3 O

O 1.

Non-Routine, Non-Radiological Environmental Report No. 50-313/75-.,7 2.

Report Date:

9/S/75 3.

Occurrence Date:

9/3/75 4.

Facility:

Arkansas Nuclear One-Unit 1 Russellville, Arkansas 5.

Identification of Occurrence:

Chemical concentration of ammonia increased across the plant equal to the Environmental Technical Sp.ecification limit.

~

6.

Conditions Prior to Occurrence:

Steady-State Power X

Reactor Power 2363 bMth Hot Standby Net Output 778 Mwe Cold Shutdown Percent of Full Power 92 %

Refueling Shutdown Load Changes During Routine Power Operation Routine Startup Operation Routine Shutdown Operation Other (specify) s i

7.

Description of Occurrence:

Samples taken from the intake and discharge canal indicate that ammonia concentration in the discharge canal was 0.05 mg/l greater than ammonia concentration in the intake canal.

e e

d 8004110b$7 d

w

---,-e--

e

s Non-Routine, Non-Radiological Environmental Report No.

50-313/75-47 l

8.

Designation of Apparent Cause of Occurrence:

Design Procedure Manufacture Unusual Service Condition Including Environmental Installation /

Construction Component Failure Operator Other (specify)

X Neutralizing tank draining into discharge fiume at time of sampling.

4 9.

Analysis of Occurrence:

The neutralizing tank which contains water impurities remaining after regenerating condensate demineralizers and plant makeup water deminer-alizers was being drained into the discharge flume when samples were 3

taken. No other liquid releases were in progress at the time of sampling.

~:

-l 4

l 1

(

l

e m

Non-Routine, Non-Radiological Environmental Report No.

50-313/75-47 10.

Corrective Action:

i Revisions to our Environmental Technical Specifications concerning chemical discharges have been prepared and submitted to.the NRC for approval.

f i

4 11.

Failure Data:

The circumstances of this report are similar to those reported in Non-Routine, Non-Radiological Environmental Reports No. 50-313/75-28 through 50-313/75-46.

s

\\