Y.Ce
. PHILADELPHIA ELECTRIC COMPANY 2301 M ARKET STREET P.O. BOX 8699 PHILA DELPHI A. PA.19101 I
1215) D 41 4000 i
tatswisainc amo atssamen of,anime nt l
l Mr. Boyce 11. Grier, Director, Region I United States Nuc1 car Regulatory Commission 631 Park Avenue King of Prussia, Pa.
19406 SUBJECr:
NRC Region I Letter dated February 6,1980 Re:
IE Bulletin No. 80-03 Loss of Charcoal from Standard Type II, i
2 Inch, Tray Absorber Cells Limerick Generating Station, Units 1 and 2 Docket Nos. 50-352 and 50-353 FILE:
COVT 1-1 (IE Bulletin 80-03)
Dear Mr. Grier:
Philadelphia Electric Company has reviewed IE Bulletin No. 80-03 submitted with the subject letter received on February 8, 1980.
4 At Limerick Generating Station, both Units 1 and 2 have tray type charcoal filters which utilize tack we'ds on one and three quarter inch (13/4") centers to secure the perforated screens to the tray casings.
With this close tack weld spacing, the charcoal filters will not be susceptible to the charcoal leakage problems discussed in this bulletin.
The tray type charcoal filters were purchased from American Air Filter Company and have not yet been delivered to the job site. When received at the site, we.will verify that the screen. attaclunent spacing is as reported.
Based on the above, we plan no further action on this item.
Sincerely, W
J. S. Kemper', Vice President Engineering & Research Department RBA/aag n
Copy to: U.S. Nuclear Regulatory Commission Office of Inspection and Enforcement Director - Division of Fuel Facility and Materials Safety Inspection Washington, D.C.
20555 8 0 0410 04;M
.