ML19309D296

From kanterella
Jump to navigation Jump to search
Certificate of Compliance 6574,Revision 5,for Model HN-200
ML19309D296
Person / Time
Site: 07106574
Issue date: 03/28/1980
From: Macdonald C
NRC OFFICE OF NUCLEAR MATERIAL SAFETY & SAFEGUARDS (NMSS)
To:
Shared Package
ML19309D291 List:
References
NUDOCS 8004100224
Download: ML19309D296 (3)


Text

-

O V

Form NRC 618 U.S. NUCLEAR REGULATORY COMMISSION

[CFR 71 8

CERTIFICATE OF COMPLIANCE For Radioactive Materials Packages 1.fa) Certificate Number 1.(b) Revision No.

1.(c) Package Identification No.

1.(d) Pages No. 1.(e) Total No. Pages 6574 5

USA /6574/BI 1 1

3

2. PRE AM8LE 2.ta)

This certificate is issued to satisfy Sections 173.3934.173.394.173.395, and 173.396 of the Department of Transportation Hazaidous Materials Regulations (49 CFR 170189 and 14 CFR 103) and Sections 146-19-10a and 146--19-100 of the Department of Transportation Dangerous Cargoes Regulations (46 CFR 146-149), as amended.

2.(b)

The packaging and contents described in item 5 below, meets the safety standards set forth in Subpart C of Title 10, Code of Federal Regulatons, Part 71, " Packaging of Radioactive Materials for Transport and Transportation of Radioactive Material Under Certain Conditions."

2.fc)

This certificate does not rehave the consignor from compliance with any requirement of the regulations of the U.S. Department of Transportation or other applicable regulatory agencies, including the government of any country through or into which the package will be transported.

3. This certificate is assued on the basis of a safety analysis report of the package design or application-3.(a)

Prepared by (Name and address):

3.(b)

Title and identification of report or application:

Hittman Nuclear and Development Hittman Nuclear and Development application Corporation dated December 10, 1979, as supplemented.

l 9190 Red Branch Road Columbia, MD 21045 3.(ci oockei No. 71-6574 4 CONDITIONS This certificate is conditional upon the fulfilling of the requirements of Subcat O of 10 CFR 71, as applicable, and the conditions specified in item 5 below.

5. Description of Packaging and Authorized Contents, Model Number, Fissile Class, Other Condituans, and

References:

(a ) Packaging (1) Model No.: HN-200 (2) Description The packaging consists of a ' steel-lead-steel annulus cask fabricated in the form of a right circular cylinder and three different types of inner containers. The shielded cask, closed at one end and a lid closure at the other, is 66.25 inches in diameter by 74.5 inches in height. The cask wall consists of a 3/8-inch inner steel shell, 3-3/4 inches of, lead shielding, one inch. outer steel shell, and a steel flange connecting the two shells.

  • The cask outer shell is surrounded by a one inch layer of insulating material and canned in 14-gauge steel.

The lid, sealed by a Viton 0-ring, is of similar construction and is bolted to the cask body. A cylindrical shield plug is located in the center of the cask lid and is sealed by a Viton 0-ring.

Lifting and tie-down devices are attached to the cask body and impact skirts, consisting of removable rings of shock absorbing foam, are attached to the ends of the cask..*

(3) Drawing The package is fabricated in accordance with the following Hittman Nuclear and Development Corp. Drawing No.: C001-5-9200, Sheets 1 through 6, Revision I. -

80041 on 22(

Page 2 - Certificate No. 6574 - Revision No. 5 - Docket No. 71-6574 5.

(b) Contents (1) Type and form of material The package contents consist of large quantities of nonfissile radioactive wastes solids. These solids include spent ion exchange resins, filter sludges, evaporator concentrators and spent fuel cartridges.

(2) Maximum quantity of material per package The cask contents shall be contained within one of the following inner containers and limited as follows:

(a) A single disposable inner container consisting of a right circular steel cylinder with a positive leaktight closure cap at the top. A maximum decay heat load of 205 Btu /hr.

(b) The HN-200-30 inner configuration consists of two tiers of four, 30-gallon D0T Specification 17H steel drums and two steel four-drum pallets. A maximum decay heat load of 84 Btu /hr.

(c) The HN-200-55 inner configuration consists of one tier of three 55-gallon, 00T Specification 17H steel drums positioned on one steel pallet. A maximum decay heat load of 116 Btu /hr.

6.

The total weight of the shipping container shall not exceed 48,000 pounds and the weight of the contents shall not exceed 10,675 pounds.

7.

Wooden battens shall be provided in the shipping cask cavity sufficient to prevent significant movement of the contents relative to the shield plug under normal or accident conditions.

8.

Prior to each shipment, the packaging'Viton 0-rings lid seals shall be inspected.

The seals shall be replaced with new seals if inspection shows any defects or every twelve (12) months, whichever occurs first.

9.

The package authorized by this certificate is hereby approved for use under the general license provisions of 10 CFR 571.12(b).

10. Expiracion date: March 31, 1985.

l l

?

m

c Page 3 - Certificate flo. 6574 - Revision No. 5 - Docket No. 71-6574 REFERENCES Hittman Nuclear and Development Corporation applicated dated December 10, 1979.

Supplement dated: March 20, 1980.

FOR THE U.S. NUCLEAR REGULATORY COMMISSION h

-

Charles E. MacDonald, Chief Transportation Certificaticn Branch Division of Fuel Cycle and Material Safety 1960 Mg 2 B Date:

m F

k