ML19309D158

From kanterella
Jump to navigation Jump to search
Advises That IE Info Notice 80-08, States Co Sliding Link Electrical Terminal Block Was Sent to Listed Utils on 800307
ML19309D158
Person / Time
Issue date: 03/10/1980
From: Carroll D
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To: Wright G
ILLINOIS, STATE OF
References
NUDOCS 8004100089
Download: ML19309D158 (2)


Text

_.

f-.s'o e

UNITE D STATES c

8' 3

NUCLEAR REGULATORY COMMISSION 3 y, E

REGION lil

~

o '

[

799 ROOSEVELT ROAD g,.....f GLEN ELLYN. lLUNOIS 60137 3AR 10 B00 State of Illinois Department of Public Health ATTN:

Mr. Gary N. Wright, Chief Division of Nuclear Safety 535 West Jefferson Street Springfield, IL 62761 Gentlemen:

The enclosed IE Information Notice No. P0-08 titled "The States Company Sliding Link Electrical Terminal Block" was sent to the following licen-sees on March 7, 1980:

American Electric Power Service Corporation Indiana and Michigan Power Company D. C. Cook 1, 2 (50-315, 50-316)

Cincinnati Gas & Electric Company Zimmer (50-358)

Cleveland Electric Illuminating Company Perry 1, 2 (50-440, 50-441)

Commonwealth Edisc a Company Braidwood ', 2 (50-456, 50-457)

Byron 1, 2 (50-454, 50-455)

Dresden 1, 2, 3 (50-10, 50-237, 50-249)

La Salle 1, 2 (50-373, 50-374)

Quad-Cities 1, 2 (50-254, 50-265)

Zion 1, 2 (50-295, 50-304)

Consumers Power Company Big Rock Point (50-155)

Midland 1, 2 (50-329, 50-330)

Palisades (50-255)

Dairyland Power Cooperative LACBWR (50-409)

Detroit Edison Company Fermi 2 (50-341)

Illinois Power Company Clinton 1, 2 (50-461, 50-462) 8 004100g [fj

c State of Illinois

  • Iowa Electric Light & Power Company Duane Arnold (50-331)

. Northern Indiana Public Service Company Bailly_(50-367)

Northern States Power Company Monticello (50-263)

Prairie Island ~1, 2 (50-282, 50-306)

Public Service of Indiana Harble Hill 1, 2 (50-546, 50-547)

Toledo Edison Company Davis-Besse 1 (50-346)

Union Electric Company Callaway 1, 2 (50-483, 50-486)

Wisconsin Electric Power Company Point Beach 1, 2 (50-266, 50-301)

Wisconsin Public Service Corporation Kewaunee (50-305)

Sincerely, MllW

, \\s 6

. c.

rothy E.

arroll, Acting Chief Administra ive Branch

Enclosure:

IE Information Notice No. 80-08 cc w/ encl:

Mr. D. W. Kane, Sargent & Lundy

' Central Files Reproduction Unit NRC 20b Local PDR NSIC TIC

SSINS: 6870 i

UNITED STATES Accession No.:

NUCLEAR REGULATORY COMMISSION 7912190689 0FFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.

20555 March 7, 1980 IE Information Notice No. 80-08 THE STATES COMPANY SLIDING LINK ELECTRICAL TERMINAL BLOCK Description of Circumstances:

On July 19, 1979, the Consumers Power Company notified the Nuclear Regulatory Commission of a defect found in the sliding link electrical terminal block manufactured by the States Company, a subsidiary of Multi Amp Corp.

The defective terminal blocks were found at the Midland plant.

The connection between the two slotted bars on the terminal block is made by a U-shaped sliding link and spacer located between the two bars.

The top of the U-shaped link and the spacer are drilled and the bottom of the link is threaded to accept a 8-32 screw. When the screw is tightened it binds the link, spacer and bar together to make electrical connection.

Loosening the screw and sliding the link from between the bars breaks the connection.

The purpose of the link is to provide easy insertion of test instruments, etc.

into the circuit.

The defect, which has been identified in 5% of the terminal blocks checked, occurs in the form of a crack between the threaded screwhole and the side of the U shaped link.

When the screw is tightened the crack widens and a poor or intermittent electrical connection can result.

A defective link is impossible to cinch tightly in place and is difficult to detect visually. shows the States Company terminal block.

The defect, a crack in the bottom portion of the metal U-shaped link, is displayed in the exploded view of the terminal block assembly.

These terminal blocks are widely used in the nuclear industry and may be used as permanent installations in safety related systems.

The defective mechanical connection can cause an electrical circuit malfunction, This Information Notice is provided to inform licensees of a potentially significant matter.

It is expected that recipients will review the informa-tion for applicability to their facilities.

No written response to this IE Information Notice is required.

However, the reporting requirements as set forth in the regulations must be met.

If you require additional information regarding this matter, contact the Director of the appropriate NRC Regional Office.

Enclosure:

Graphic Display of Terminal Block

ENCLOSURE 1 TO IE INFORM ATION NOTICE 80-08 t

I m,

7;--

t l

r1 "ll l

f}

u

~

M2 Side View of States Company Terminal Block in Assembled Position

')

Mi W

Ij?

'M l

Cracks in

' U.She ed Link L.

Exploded View of States Company Terminal Block

{

,~

e IE Information Notice No. 80-08 Enclosure March 7, 1980 RECENTLY ISSUED IE INFORMATION NOTICES Information Subject Date Issued To Notice No.

Issued 80-07 Pump Shaft Fatigue Cracking 2/29/80 All Light Water Reactor Facilities holder power reactor OLs and cps 80-06 Notification of Significant 2/27/80 All holders of Reactor Events OLs and to near term OL applicants 80-05 Chloride Contamination 2/8/80 All licensees of nuclear of Safety Related Piping power reactor facilities and applicants and holders of nuclear power reactor cps 80-04 BWR Fuel Exposure in 2/4/80 All BWR's holding a-Excess of Limits power reactor.0L or CP 80-03 Main Turbine Electro-1/31/80 All holders of power Hydraulic Control System reactor OLs and cps 80-02 8X8R Water Rod Lower 1/25/80 All BWR Facilities End Plug Wear holder power reactor OLs or cps 80-01 Fuel Handling Events 1/4/80 All holders of power reactor OLs and cps 79-37 Cracking in Low Pressure 12/28/79 All power reactor OLs Turbine Discs and cps 79-36 Computer Code Defect in 12/31/79 All power reactor OLs Stress Analysis of Piping and cps Elbow 79-35 Control of Maintenance 12/31/79 All power reactor facilities and Essential Equipment with an OL or CP 79-34 Inadequate Design of 12/27/79 All holders of power reactor Safety-Related Heat OLs and cps Exchangers

.