Discusses Incorrect Testing of Concrete Test Cylinders on Tinius-Olson Test machine.Twelve-inch Head Was Used When Head No Longer than 10-inches Should Have Been Used. Indicated Strength Was Probably Not Significantly Affected
ML19309B545
Person / Time
Site: Wolf Creek 
Issue date: 02/08/1980
From: Koester G
KANSAS GAS & ELECTRIC CO.
To: Seidle W
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
NUDOCS 8004040264
Download: ML19309B545 (1)


Text

((C KANSAS GAS AND ELECTRIC COMPANY l

GLENN L. nQ tstER

,,cc.....e........-.o.

February 8, 1980 r --

.M)y
=E ( C ' T^

I L

  • ~ '

y 6, Mr. W.C. Seidle, Chief

?Qh Reactor Construction and

{b Engineering Support Branch ll k

{g g g g U.S. Nuclear Regulatory Commission i

. Region IV 611 Ryan Pla::a Drive

'~

Suite 1000 Arlington, Texas 76011 Re: Docket No. STN 50-482 Sub: Tinius-Olson Concrete Cylinder Compressive Strength Testing Machine

Dear Mr. Seidle:

On January 7, 1980, Mr. M.E. Clark advised Mr. W.A. Crossman that a number of concrete test cylinders from the Wolf Creek Project had been tested on a new Tinius-Olson test machine using a twelve-inch head, whereas a head no larger than ten inches should have been used.

Our investigation into this matter has not been completed, however, our preliminary conclusion is that use of a twelve-inch head does not significantly affect the indicated concrete cylinder strength and that any slight error which may have been introduced is in the conservative direction.

It is also our preliminary judgment that had this error not been discovered, no reduction in the safety of operations, throughout the life of the unit, would have resulted and, therefore, regulation 10CFR50.55(e) is not applicable.

We expect to conclude our investigation and report further on this matter by April 1, 1980.

Yours very truly, g;7) h GLK:bb h

8004040 M i

201 N. Market - Wichsta. Kansas - Mail Address: P.O. Box 206 i Wuchota. Cansas 67201 - Telephone: Area Code (316) 261-6451

'