ML19309A223

From kanterella
Jump to navigation Jump to search
Notice of Violation from Insp on 771115-18 & 21
ML19309A223
Person / Time
Site: Rancho Seco
Issue date: 12/05/1977
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION V)
To:
Shared Package
ML19309A219 List:
References
50-312-77-16, NUDOCS 8003260925
Download: ML19309A223 (1)


Text

-

l(Q

~%

t.

O-4 APPENDIX A Sacramento Municipal Utility District 6201 S. Street P. O. Box 15830 Sacramento, California 95813 Docket No. 50-312 License No. DPR-54 Notice c' Violation Based on the results of the NRC 'r.: ::tinn conducted on November 15-18 and 21, 1977, it appears that certain of the activities at your Rancho Seco facility were not conducted in full compliance with the conditions of NRC Facility License No. DPR-54 as indicated below.

Item A is an infraction, and item B is a deficiency.

O*

A.

Contrary to paragraph 4.4.1.3 of the Technical Specifications,.

which requires remotely operated R.1ctor Building isolation valves to be stroked every three months, one group of seven valves covered by Surveillance Procedure No. 205.07B was not stroked between October 3,1976 and April 6,1977.

B.

Contrary to paragraph 6.9.1 of the Technical Specifications and paragraph B.2.b(4) of Regulatory Guide 1.16, a cracked decay heat system socket weld discovered by the licensee on October 28, 1977, was not reported in writing to the NRC within 30 days.

O 8003 260 [J [

.