ML19308C884
| ML19308C884 | |
| Person / Time | |
|---|---|
| Site: | Crane |
| Issue date: | 05/12/1978 |
| From: | Case E Office of Nuclear Reactor Regulation |
| To: | Gossick L NRC OFFICE OF THE EXECUTIVE DIRECTOR FOR OPERATIONS (EDO) |
| References | |
| TASK-TF, TASK-TMR NUDOCS 8002070635 | |
| Download: ML19308C884 (1) | |
Text
_
s
/ a atog**
- m UNITED STATES
g y*
NUCLEAR REGULATORY COMMISSION 3
, j WASHINGTON, D. C. 20655 t.
'% ".... # p May 12,1978
^m MEMORANDUM EOR: Lee V. Gossick, Executive Director for Operations E. G. Case, Chairman, Regulatory Requirements FPOli
=
Review Committee SU8AJEX.T SUFtMRY OF REGULA'IORY REQUIREFECS REVIEW COff4ITI'EE l
MEETING 140. 73, MAY 2, 1978.
,a ne Comittee reviewed:
i i
1.
Draft Regulatory Guide, "JdMTPHERIC DISPERSI04 MODELS FOR POI'DCIAL ACCIDCJT CONSEQUENCE ASSESSMCCS AT NUCLEAR POWER PIACS" dated Feoruary 3, 1978, and l
ATMOGPHERIC DISPERSIQi MODEL FOR ACCIDCC EVALUATIONS dated April 18, 1978.
Se Comittee recommended that the Director, Office of Standards I
Developnent prepare on an expedited schedule an Information Paper for l
the Comission. mis Information Paper should discuss the new model, i
compare it to the current model, outline various alternatives, and indicate our intentions concerning the use of the new model.
d Pending the preparation and RRRC review of this Information Paper, the Comittee recommended that in the interim:
a.
Se staff should allow applicants to use either the current l
model or the proposed new model.
?
I o.
Se proposed new model should have specific 1 nguage a6ded to j
indicate that tne selected x/0 value will be equalled or exceeded less than a total of 5 percent of the time arourx! the site boundary.
Item 2 of the agenda was deferred to a later meeting.
w Edson G. Case, Chairman Regulatory Regairements Review Comittee q
ccs:
See next page
/
t 8002070o N p'
_ _ _ _ _. _ _.. _ _ _.. _