ML19308B826

From kanterella
Jump to navigation Jump to search
Submits Recommended Customer Guidelines Re Hpis Actuation of Hpis/Lpis Should Not Be Bypassed Under Any Condition Except Normal,Controlled Plant Shutdown
ML19308B826
Person / Time
Site: Crane, Davis Besse  
Issue date: 11/01/1977
From: Joseph Kelly
BABCOCK & WILCOX CO.
To: Finnin R, Karrasch B, Swanson E
BABCOCK & WILCOX CO.
References
TASK-TF, TASK-TMR NUDOCS 8001170393
Download: ML19308B826 (1)


Text

.

.c

- -.,d

/

L l

THE BABC0CX & WILCOX COMPAtlY p

i

~

h

' POWER GEllERATION GROUP

.Ta l

}

Distribution From

/

i J. J. Kelly, Plant Integration gj/

aos ees.s Cust.

File No.

or Ref.

Generic Subj.

Date Customer Guidance On High Pressure Injection Operation November 1, 1977 l m. i... i.....,..........,........ mi.

..s,.

DISTRIBUTION B. A. Karrasch /

D. W. IaBelle E. W. Swanson N. S. Elliott R. J. F1enin D. F. Hallman /

B. M. Dunn /

~

Two recent events at the Toledo site have pointed out that perhaps we are not giving our custo=crs enough guidance on the operation of the high pres -

sure injection systes. On Septe=ber 24., 1977, after depressurizing due to a stuck open electromatic relief valve, high pressure injection was auto-matically initiated. The operator stopped HPI when pressurizer. level began to recover, without regard to primary pressure. As a result, the transient continued on with boiling in the RCS, etc.

In a similar occurrence on October 23, 1977, the operator bypassed high pressure injection to prevent initiation, even though reactcr coolant system pressure went below the actuation point.

[.

Since there are accidents which require the continuous operation of the high pressure injection system, I wonder what guidance, if any, we should be giv-ing to our customers on when they can safely shut the system down following an accident? I recommend the following guidelines be sent:

\\

[#

a) Do not bypass or otherwise prevent the actuation of high/ low

'7 pressure injection under any conditions except a nor=al, controlled plant shutdown.

' t" h

b) Once high/ low pressure injection is initiated, do not stop it unless:

h Tave is stable or decreasing and pressurizer level is increasing and

,h primary pressure is at least 1600 PSIG and increasing.

I would appreciate your thoughts on this subject.

h fp0W

~

1 f ~~~~~

m sy

&jf. $ftS. '

h

'~

(aw Sw soo u go 3 9.3

~~

A b m&

d,J s > p$4 j f 7~

"ZP/' ".J Ad-per/

. 4 e nudu axC 9 u s &.

wnc.,

JJK:jl

.