O w - --- -- --
O METRO; OhlTAN EDISC CO'1PANY sumo:moramtm. 3ucununtscovannav 3 (,,
' CST OFFICE BOX 480 MIDDLETOWN. PENNSYLVANIA 17057 TELEPHONE 717-044-4M1 May 28,1974'
'D D
Mr. J.P. O'Reilly, Director' Directorate of Regulatory Operations Wi Region I F %] 3ri b
". E'. 3 O@j 631 Park Avenu a
King of Prussf a.. Fa.
19405 0
Operating License DPR Decket 50-2E9
Subject:
Abnomal Occurrence No. A0 74-5
Dear Mr. O'Reilly:
This telegram is to confirm a conversation betvam H.W. Crocker (Region'I-DRO),
and J.G. Herbein (TNI-Superintendent) at 1503 HRS 25 May 1974.
Violation of the Enviromntal Technical Specification-2.1.a. (2) (page 3) in that service water discharge differential tegerature was decreased at a rate exceeding 20F/hr..on 26 May.
Durine cocid:wn 6f the RCS, the difference between service water discharce tenerature to the river and plant inlet river water-tenperature was changed fron +70 AT to 00 AT ever a une hour period. The decrease in differential ter:perature c: curred when the service water cooling tower fans were er,ergized.
Upon, indication that the differentfal teccerature had changed at a rate exceading 20 ai per hour the n=1ber of cooling to ver fans in operation was reduced to one.
The service water cooling tower fans mthod of operation was adjusted to caintain
. differential te perature decreasa-at less than 20F/hr.-
Very truly yours,.
j' bW
.G. Herbein Statien Superintendent TNI. Nuclear Station
{
JGI/dm
/(f; O
O 1910sso 7 3 2 S
.