2PMONE7T7-944-4041
~
June 6L 1974 Mr. J.P. O'Reilly, Director Ofrectorate of Regulatory Operations Region I 631 Park Avenue King of Prussia, Pa.
19405
~
Operating License DPR-50 Docket 50-289 Subfect: Ehifromental Incident No. EI 74-4'
Dear P!r. O'Ref1Ty:
Titis teicgram is to confim a conversation between D.'Sterberg (Region I-DRO),
and J.G. F,ertein (TMI Superfntendent) at 1030 HRS. 6 June 1974.
Violation of the Envirorcental Technical Specification 2.2.1.a (page 7) in that the total chlorine coc:ponent renured at the plant r1Y6r discharge exceeded.2 pp on 6 June 1974.
Analpis of the total chlorine cceponent in the plant river discharge 10 minutes after the start of a chierination cycle indicated.215 p;n, at 30 minutes indicated.22 pp. and at 50 minutes ir4tcated.25 pps The chlorine. addition rate hn been reduced frca 250 f/ day to 200 f day.
c V y truly yours, j
^
(JtG.Herbein Station Superintsadent THI ituclear Station-JGl/ dam D
m ic m r
k.J0_.J] _ i{
A la
" k)
' niono Q$'/
i
~
3
. -.