i O

TMI-I OPERATING

SUMMARY

The Unit remained shutdown the entire month by order of the NRC as a result of the TMI-II incident of March 28, 1979.

MAJOR SAFETY RELATED MAINTENANCE While in the cold shutdown mode of operation the Decay Heat Pump 1B motor tripped and was severely damaged as a result of a loss of lubricating oil. The motor was removed and a temporary, higher capacity air motor was installed in its place.

The temporary motor was sufficiently tested for temperature, current, and vibration prior to return to operation.

A new " original" replacement motor is on order and will be installed prior to Unit I's return to power.

1 s

790827gqqq

-?

(

REFUELING INFORMATION REQUEST 1.

Name of Facility:

Three Mile Island Nuclear Station, Unit 1 2.

Sqheduled date for next refueling ' shutdown:

Unknown 3.

Scheduled date for restart following refueling:

Unknown h.

Will refueling or resumption of operation thereafter require a technical specification change or other license amendment?

If answer is yes, in general, what will these be?

If answer is no, has the reload fuel design and core configuration been reviewed by your Plant Safety Review Committee to determine whether any unreviewed safety questions are associated with the core reload (Ref.

10 CFR Section 50.59)?

If no such review has taken place, when is it scheduled?

Amendment No. 50, Cycle 5 reload, was approved on 3-16-79 5

Scheduled ' ante (s) for submitting proposed licensing action and supporting information:

N/A 6.

Important licensing considerations associated with refueling, e.g. new or different fuel design or supplier, unreviewed design or performance analysis methods, significant changes in fuel design, new operating procedures:

N/A j

7 The number of fuel' assemblies (a) in the core, and (b) in the spent fuel storage pool:

(a) 177 (b) 212 8.

The present lice 4 sed spent fuel pool storage capacity and the size of any increase ir. liceased storage capacity that has been requested or is pinnned, in ni:mher or fuel nnnemblien:

i Tlie prenent, l leennoil esipete t Ly in 75:'.

'I'he ro stre no pl etntieel inc rennen at thin time.

l 9

The projected date of the innt refueling that can lie dincharged at the spent fuel pool assuming the present licensed capacity:

1986 is the last refueling discharge which allows full core off-load capacity (177 fuel assemblies).

AVERAGE DAILY UNIT POWER LEVEL Docket No.

50-289 Unit i

Date

_ August 15. 1979 Completed By D. G. Mitchell Telephone 215-921-6579 DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (MWe-Ne't)

(MWe-Net) 1

-h 17

_h 2

-h 18 b

3

-h 19

-h h

-5 20

-h 5

-5 21

-4 6

-5 22

-4 7

-5 23

-h 8

h 2h

-h 9

-h

-h 25 10

-5 26

-4 11

-h

-h 27 12

-h 28

-h 13

-b

-h 29 14

-4 30

-h

-4 15 31

-h 16

-h

(

f U

1 ERATING DATA REPORT I.kst No.

50-289 Date August 15, 1979 Complettd By D. G. Mitchell OPERATING STATUS Telephone 215-921-6579 1.

Unit Name:

Three Mile Inland Unit. 1 2.

Reporting Period:

July 1979 3.

Licensed Thermal Power (MWt):

2535 k.

Nameplate Rating (Gross MWe):

671 5.

Design Electrical Rating (Net MWe):

819 6.

Max. Dependable Capacity (Gross MWe):

8h0 7

Max. Dependable Capacity (Net MWe):

776 8.

If Changes Occur in Capacity Ratings (Items No. 3 through 7) Since Last Report, Give Reasons:

9 Power Level to which Restricted. If Any (Net MWe):

10.

Reasons for Restrictions, If Any:

11.

Hours in Reporting Period Thh 5087 h1056 12.

No. of Hours Reactor was Critical 0.0 llos.n 3,73, n 13 Reactor Reserve Shutdown Hours 0.0 0.0 838.5 lb.

Hours Generator On-Line 0.0 1128.0 31180.9 15 Unit Reserve Shutdown Hours 0.0 0.0 0,0 0

2828448.

76531071.

16. Gross Thermal Energy Generated (MWH) 17 Gross Elect. Energy Generated (MWH)

U 945996.

25464330.

18. Net Electrical Energy Generated (MWH)

-3236.

865024.

23857039 0.0 22.2 72.h 19 Unit Service Factor 20.

Unit Availability Factor 0.0 22.2 72.h

-0.6 21 9 70.2 21.

Unit Capacity Factor (Using MDC Net) 22.

Unit Capacity Factor (Using DER Net)

-0.5 20.8 67.7 100.0 72.2 12.6

23. Unit Forced Outage Rate 2h. Shutdowns Scheduled Over Next 6 Months (Type, Date, and Duration of Each):

25 If Shut Down at Egd of Report Period, Estimated Date of StartuPI Unknown

26. Units In Test Status (Prior to Commercial Operation):

FORECAST ACHIEVED INITIAL CRITICALITY INITIAL ELECTRICITY COMMERCIAL OPERATION

UNIT SHUTDOWNS AND POWER REDUCTIONS Docket No.

50-289 REPORT MONTH July 1979 Unit Name TMI-l Date August 15, 1979 Completed By n_ n_ utte.%11 Telephone 215-921-6579 l 57 No.

Date Type cv System Component Cause and Corrective h

5 O

og g'

Code h Code 5 Action to 43 g

ggo g,g Prevent Recurrence d$E 0Of MGE 3ha 1

7/1/79 F

Thh D

1 Regulatory reasons due to TMI-2 accident O'

1: Fomed 2 Reason:

3 Exhibit G - Instructions F

S: Scheduled A-Equipment Failure (Explain)

M&O B-Maintenance or Test 1-Manual f r Preparation of Data C-ReNeling 2-Manual Scram nW ee a for Meensee D-Regulatory Restriction 3-Automatic Scram Event Report (LER) File E-Operator Training & Licensee Examination h-Other (Explain)

F-Administrative G-Operational Error (Explain) 3Exhibit 1 - Same Source H-Other (Explain)

' ' ~ ~

3 m r

- - = - -