ML19305E708

From kanterella
Jump to navigation Jump to search
Forwards Rept of Alkali Reactivity ASTM C227, in Response to NRC 791213 Request for 5-month Results of Mortar Bar Test.Final Results Are Scheduled for Completion on 800419
ML19305E708
Person / Time
Site: River Bend 
Issue date: 04/07/1980
From: Weigand J
GULF STATES UTILITIES CO.
To: Seyfrit K
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
Shared Package
ML19305E709 List:
References
RBG-7464, NUDOCS 8005200297
Download: ML19305E708 (1)


Text

PDR 800520 4 A1 LPDR nc -

NSlc r

CENTRAL FILES GULF STATES UTILITIES COMPANY POSTOFFICE 8 0 x 2 9 51 BEAUVONT TEXAS 77704 AREA OCOE 713 838 663i April 7, 1980 RBG - Th6h File No. G9 5 Mr. Karl V. Seyfrit, Director U.S. Nuclear Regulatory Co-4ssion, Region IV Office of Inspection and Enforcement 611 Ryan Pla::a Drive Suite 1000 Arlington, TX 76011

Dear Mr. Seyfrit:

River Eend Station Unit 1 Docket No. 50 h58 As requested in your letter of December 13, 1979, enclosed are copies of Pittsburgh Testing Laboratory (PTL) Report numbers 800985 and SM986 for fine and coarse aggregates respectively.

Both reports show the five month results of the ASTM C227 mortar bar test being performed using high alkali cement samples.

The five moath results, recorded as an average length change percent, are +0.13 and +0.02 for fine and coarse aggregates respec-tively and are well within the acceptance limits of +0.05 for 3 month and +0.10 for 6 month test durations.

The 6 month (and final) results are scheduled for completion by April 19, 1980. We vill transmit them to you as soon as we receive them.

Sincerely, b

e_-

J G. Weigand t

Vice President Operations & Technical Systems JGW/JEB/WJR/mb Enclosures l

l

._