NITC PUELIC DCQER h C3
")
/
UNITED STATES OF AMERICA
[c y h NUCLEAR REGULATORY COMMISSION O.4 :
BEFORE THE ATOMIC SAFETY AND LICENSING BOARD Q%,
n/
In the Matter of
)
)
Docket 50-344 PORTLAND CENERAL ELECTRIC COMPANY, )
et al
)
(Control Building Proceeding)
)
(Trojan Nuclear Plant)
)
CERTIFICATE OF SERVICE I hereby certify that on December 10, 1978, Licensee's letter dated December 10, 1978 with an attached list of Requests for Design Change and other work items has been served upon the persons listed below by depositing copies thereof in the United States mail with proper postage af fixed for first class mail.
Marshall E. Miller, Esq., Chairman Atomic Safety and Licensing Board Atomic Safety and Licensing Board Panel U. S. Nuclear Regulatory Commission U. S. Nuclear Regulatory Commission Washington, D. C.
20555 Washington, D. C.
20555 Dr. Kenneth A. McCollom, Dean Atomic Safety and Licensing Appeal Division of Engineering, Ecard Architecture and Technology U. 3. Nuclear Regulatory Commission Oklahoma State University Washington, D. C.
20555 Stillwater, Oklahoma 74074 Robert M. Johnson, Esq.
Dr. Hugh C. Paxton Assistant Attorney General 1229 - 41st Street 100 State Office Building Los Alamos, New Mexico 87544 Salem, Oregon 97310 l
Joseph R. Gray, Esq.
Lowenstein, Newman, Reis, Axelrad & Toll Counsel for NRC Staff 1025 Connecticut Avenue, N. W.
U. S. Nuclear Regulatory Commission Suite 1214 Washington, D. C.
20555 Washington, D. C.
20036 Columbia County Courthouse Mr. Eugene Rosolie Law Library Coalition for Safe Power i
Circuit Court Room 215 S. E. 9th Avenue St. Helens, Oregon 97051 Portland, Oregon 97214 Ms. Nina Bell Mr. Stephen M. Willingham 632 S. E. 18th Street 555 N. Tomahawk Drive Portland, Oregon 97214 Portland, Oregon 97217 790102026 f
o
CERTIFICATE OF SERVICE
~
Columbia Environmental Council John H. Socolofsky, Esq.
P. O. Box 611 Assistant Attorney General St. Helens, Oregon 97051 Of Attorneys for the State of Oregon 100 State Office Building Mr. John A. Kullberg Salem, Oregon 97310 Route 1, Box 250Q Sauvie Island. Oregon 97231 Gregory Kafoury, Esq.
Counsel for Columbia Environmentcl Mr. David B. McCoy Council 348 Hussey Lane 202 Oregon Pioneer Building Grants Pass, Oregon 37526 320 S. W. Stark
. Portland, Oregon 97204 Ms. C. Gail Parson P. O. Box 2992 William Kinsey, Esq.
Kodiak, Alaska 99615 Bonneville Power Administration P. O. Box 3621 Docketing and Service Section Portland, Oregon 97208 Of fice of the Secretary U. S. Nuclear Regulatory Commission Washington, D. C.
20555
.. /
O?: ; j ( iv
):DW Ronald W. Johnson Corporate Attorney Portland General Electric Company Dated: December 10, 1978
NRCPUDucu December 10, 1978 Marshall E. Miller, Esq., Chairman Atomic Safety and Licensing Board U. S. Nuclear Regulatory Commission Washington, D. C.
20555 M
/
N Dr. Kenneth A. McCollom, Dean
.0
\\
Division of Engineering, pk
.h Architecture & Technology
,N A
1 3
Oklahoma State University N
V7 Stillwater, Oklahoma 74074
'{
(4,
'0 Dr. Hugh C. Paxton J'
rg 1229-41st Street f
Los Alamos, New Mexico 67544 Centlemen:
Attached to this letter is a list of Requests for Design Changes (RDCs) which supplements previous lists. The items on this Ifst will not affect the load carrying capability of any major shear wall.
The Licensee will continue to keep the Board informed of all activities at Trojan which may be construed as being related to the Trojan Control Building.
Sincerely,
, G?l. l Lin tG g~ nr '
Ronald W. Johnson v Corporate Attorney Portland General Electric Company RWJ/LWE/4crwTICBB29 Attachment 4
)
c:
R. H. Engelken Nuclear Regulatory Commission
' Region V A. Schwencer Nuclear Regulatory Commission
k i
y ATTACHMENT Following is the list of Requests for Design Change (RDC) and other work items for which field work may be performed within the next few weeks.
The relationship of the work with the Control, Auxiliary, and Fuel Building structures is briefly summarized belcw:
RDC No.
Modification Relationship 78-095 Job No. 66: Addition A structural steel restraint will be of a restraint to the added to a 3" CVCS line at elevation CVCS line CS-2501R-28-2 87' in the Auxiliary Building.
(SR 301)78-095 Job No. 67: Modification The existing gravity support for the 14" of existing restraint for CCW line will be replaced by a structural CCW line HBD-27-1 (SR 16) steel support at elevation 56' in the Fuel Building.78-095 Job No. 68: Modification Concrete anchors will be added to the of existing restraint for existing restraint base plate for the 8" CVCS line CS-151R-5-1 CVCS line at elevation 29'in the Auxiliary i
(SR 26)
Buil ding.78-095 Job No. 69: Modification Support Steel for the existing restraint of existing restraint. for on a 3" CVCS line in the Auxiliary CVCS line CS-2501R-5-4 Building at elevation 53' will be modified.
(SR 72)78-095 Job No. 70: Modification Additional clearance will be provided for of existing restraint for the existing floor mounted restraint for CCW line HBD-22-4 a 4" CCW line in the Fuel Building at (SR 81) elevation 62'.78-095 Job No. 71: Modification Additional clearance will be provided for to existing restraint for an existing 4" CCW line floor mounted CCW line HBO-22-4 restraint at elevation 62' in the Fuel (SR 89)
Building. 095 Job No. 72:
None.
This job has been cancelled 78-095 Job No. 73: Modification Steel bracing will be added to the to existing restraint for existing restraint for a 24" CCW line at the CCW line HBD-27-4 elevation 53' in the Fuel Building.
(SR 816)
ATTACHMt'dTS, Cont.
Page Two RDC No.
Modification Relationship 78-095 Job No. 74: Modification Steel reinforcement will be added to to existing anchor for the existing anchor for a 14" CCW line the CCW line HBD-34-2 at elevation 53' in the Auxiliary 1
(SA 245)
Buil ding.78-095 Job No. 75: Modification Steel reinforcement will be added to to existing anchors for existing adjacent anchors for 14" CCW the CCW lines HBD-32-2 lines at elevation 53' in the Auxiliary (SA 250) and HBD-31-2 Building.
(SA 807)
I Field checking and design development of piping restraints has led to revisions of some of the items on lists previously submitted. The revised modifications are described below.
A work item described in the list transmitted November 28, 1978 has been revised:
RDC No.
Modification Relationship 78-095 Job No. 26 revised:
Stiffener plates and a rigid strut assem-Modification of restraint bly will be added to the existing support support steel to existing for the 24" CCW line in the Auxiliary support on CCW line Building at elevation 47'.
HBD-27-4 (SR 9)
Several work items described in the list transmitted November 30, 1978 have been revised:
RDC No.
Modification Relationship 78-095 Job No. 40 revised:
This modification provides the addition Modification of existing of restraint stiffening plates and a restraint for safety in-support beam at the floor for the existing jection line SI-2501R-1-8 4" diameter SI line restraint located in (SR 58) the Auxiliary Building at elevation 65'.78-095 Job No. 44 revised:
None.
This job has been cancelled.78-095 Job No. 47 revised:
Additional support steel will be added for Modification of support an existing anchor for the 8" RHR piping steel for the RHR piping at elevation 19' in the Auxiliary Building.
RH-60lR-7-1 (SA 68) 1
-