ML19296D209

From kanterella
Jump to navigation Jump to search
Notice of Violation from Insp on 791001-05
ML19296D209
Person / Time
Site: Calvert Cliffs  
Issue date: 11/30/1979
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To:
Shared Package
ML19296D204 List:
References
50-317-79-16, 50-318-79-13, NUDOCS 8003030008
Download: ML19296D209 (1)


Text

.

APPENDIX A NOTICE OF VIOLATION Baltimore Gas and Electric Company Docket Nos. 50-317 50-318 Based on the results of an NRC inspection conducted on October 1-5, 1979, it appears that one of your activities sas not conducted in full compliance with the conditions of your NRC Facility License Nos. DPR-53 and DPR-69 as indicated below.

Item A is a Deficiencie.

A.

10 CFR 50.59 states in part, "The holder of a license authorizing operation of a... utilization facility may... make changes in the facility as described in the safety analyses report... without prior Commission approval, unless the proposed change... involves a change in Technical Specifications... or an unreviewed safety question... a written safety evaluation... provides the basis for the determination that the change... does not involve an unreviewed safety question."

The safety evaluation for modification FCR 78-26, Fabrication and Installation of a Sleeving Platfonn, states that an unreviewed safety question is not involved since the Platform was fabricated and installed to Safety Related/ Seismic criteria.

Contrary to the above, the Sleeving Platfonn was not fabricated to Safety Related/ Seismic standards.

303 0