ML19295F972

From kanterella
Jump to navigation Jump to search
Forwards IE Info Notice 80-39, Malfunction of Solenoid Valves Mfg by Valcor Engineering Corp. No Written Response Is Required
ML19295F972
Person / Time
Site: Atlantic Nuclear Power Plant 
Issue date: 10/31/1980
From: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To: Collier A
OFFSHORE POWER SYSTEMS (SUBS. OF WESTINGHOUSE ELECTRI
References
NUDOCS 8012180008
Download: ML19295F972 (1)


Text

i

  • e arag UNITED STATES

/

o

~

! }

,.,q NUCLEAR REGULATORY COMMISSION 1

e REGION 11 1o1 MARBETTA sT.. N.W., sulTE 310o o

g'

/

ATLANTA, GEORGIA 3o3o3 5

OCT 311980 In Reply Refer To:

RII;JPG 60-4373 Offshore Power Systems ATI'N:

A. R. Collier, President P. O. Box 8000 Jacksonville, FL 32211 Gentlemen:

The enclosed Information Notice provides early notification of an event th.t may have safety significance. Accordingly, you should review the Information Notice for possible applicability to your facility.

No specific action or response is requested at this time; however, contingent upon the results of further staff evaluation, a Bulletin of Circular recom-mending or requesting specific licensee actions reay be issued.

If you have questions regarding this matter, please contact me.

Sincerely, wM ms u~~-f James P. O'Reilly Director

Enclosures:

1.

IE Information Notice No. 80-39 w/ Enclosure 2.

List of Recently Issued IE Information Notices 8012]80607

UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D. C. 20555 October 31, 1980 IE INFORMATION NOTICE NO. 80-39 MALFUNCTION OF SOLEN 0ID VALVES MANLTACTURED BY VALCOR ENGINEERING CORPORATION PURPOSE:

The intent of this Informatica Notice is to alert holders of construction permits and operating licenses for nuclear power plants of a potentially generic problem involving the malfunctioning of certain solenoid valves manu-factured by the Valcor Engineering Corporation (Valcor).

The solenoid valves so involved are designated as Valcor Valve Model No. V52600-554-1.

Valcor has informed us that these valves have only been supplied to the McGuire facility; however, since these valves were substituted for solenoid valves of another manufacturer that did not meet the requirements of IE Bulletin No. 79-01 and its amendments, licensees and holders of construction permits should take into account the problem identified in this Information Notice prior to making any similar substitution.

BACKGROUND:

By LX dated June 27, 1980, Valcor submitted a preliminary 10 CFR Part 21 Report addressing the malfunctioning of Valcor solenoid valves at the McGuire facility. The malfunctioning valves have been identified as Valcor Valve Model No. 52600-554-1.

This 5X was subsequently followed by a letter dated July 3, 1980, transmitting a more detailed Part 21 Report entitled," Quality Assurance Report", a copy of which is attached hereto as Enclosure No. 1.

In brief, the malfunction appears to be an intermittent type wherein the valve fails to cycle from OPEN to CLOSE to OPEN immediately after a sustained period of operation in the energized (OPEN) mode. Although the valves are rated for

" continuous operation", Valcor contends that the valves were not designed to meet the operating conditions requiring the imediate cycling from OPEN to CLOSE to OPEN after a sustained period of continuous energization. A major source of the problem, therefore, may be a misunderstanding of the term

" continuous operation". By letter dated July 14, 1980 to Duke Power Company, Valcor transmitted itr recomendations in this matter entitled, " Outline -

Suggested Modification Procedures", a copy of which is attached hereto as Enclosure No. 2.

Enclosures:

1.

Quality Assurance Report DUPLICATE DOCUMENT Entire document previously entered into system under:

ANO D@

No. of pages:

(p