ML19294B758

From kanterella
Jump to navigation Jump to search
Forwards Addl Info to Fire Protection Review of Item 3.1.5 Re Gas Suppression Sys
ML19294B758
Person / Time
Site: Maine Yankee
Issue date: 02/28/1980
From: Randy Hall
BROOKHAVEN NATIONAL LABORATORY
To: Ferguson R
Office of Nuclear Reactor Regulation
References
NUDOCS 8003050475
Download: ML19294B758 (2)


Text

..

A

~

BROOKHAVEN NATIONAL LA.BORATORY ASSOCIATED UNIVERSITIES, INC.

f Upton. New Ycrk 11073 Cecccment of Nue:ecr Energy (5 to) 345-2144 February 28, 1980 50 4 9 Mr. Robert L. Ferguson Plant Systems Branch U.S. Nuclear Regulatory Commission Washington, D.C.

20555 RE: Maine Yankee, Fire Protection Review, Additional Infonaation on Item 3.1.5

Dear Bob:

At the request of Leo Derderian, we have prepared the attached additional information on Item 3.1.5, Gas Suppression System.

Respectfully yours, obert E. Hall, Group Leader Reactor Engineering Analysis REH:EAM:sd attachment cc.:

R. Cerbc;e wo/att.

L. Derderian W. Kato wo/att.

E. MacDougall V. Panciera E. Sylvester

~

Aoob s

}ll 8 003050 p

47g

..s MAINE YANKEE Fire Protection Review Item 3.1.5 - Gas Suppression System (Additional Information)

The following is additional information pertaining to our letter of Feoruary 8,1980 which was an evaluation of Maine Yankee's submittal on SER Item 3.1.5.

In this letter we concluded that the. licensee's submittal pertaining to the installation of an automatic Halon fire suppression system in the control room cable chase was unacceptable because it lacked the design concentration and soak time for the proposed system.

The letter also stated that the submittal contained no information on subitems B and C of this item pertaining to the proposed generator bearing gas suppression system and the change from manual to automatic actuation of the existing CO2 system in the protected cable tray roan.

In order to close out item 3.1.5, we recommend that the staff request that the licensee be directed to include the following features in their proposed Halon fire suppression system at the control room cable chase:

"The cable chase in the control room should be provided with a Halon 1301 fire suppression system designed to the applicable provisions of NFPA 12A; with provisions for two discharges each capable of producing a 7% concen-tration for 10 minutes. Automatic actuation of the system should be ini-tiated by cross zoned ionization type fire detectors.

Subitems B and C of this item do not require a submittal from the licensee be-cause these were not design review items in the SER. Accordingly, our letter which indicated that the licensee should provide additional information on these subitems was in error suggesting that the licensee be required to submit this information.

e G

G O