Responds to IE Bulletin 80-17,Suppl 4, Failure of 76 of 185 Control Rods to Fully Insert During Scram at Bwr. Full Compliance Will Be Delayed,Pending Receipt of Electronic Parts by 810130
ML19291D152
Person / Time
Site: Browns Ferry  
Issue date: 01/20/1981
From: Cross J
TENNESSEE VALLEY AUTHORITY
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
IEB-80-17, NUDOCS 8102030211
Download: ML19291D152 (2)


Text

j, _ ;n77, '

/jb i

1

?Qk ShWhfE Y*

USNRC HCG:. *,

s Tt MITs, M~

Tb: Hwa %e m

a= Q JC!20 T&xng9 scc VAuuer AUTHonnTY NK ' crixi' RKs.E gy 2Y2/ggg3 cuarrawoosa, Tcwwerssa suoi gf

' 4 c- -g 500A Cheutnut Street Tower 11 8

  1. s,. @M ff* l 'E m M m g

h'# Q[

U January 20, 1981 l

gg 6 5 7 ~ '2 0 W

  1. ~~

' h.

p

_ \\.C'd

-M Ig" Director s s Deputy Director 0

IM b j

Ass

  • t to Directo Mr. James P. O'Reilly, Director Admin. Of ficer Orrice or Inspection and Enroceement RONS Chief
  1. ( p U.S. Nuclear Regulatorv Commisalon RCES Chief

~

Re6 on II - Suite 3100 FFMS Chief

-b 1

101 Marietta Street Sfgds Chief At3nnta, Georgia 30303 P A Officer

_., nw

Dear Mr. O'Reilly:

OFFICE OF INSPEJCT 03 AND ENFORCFHBNT BULLETIN S0-17, SUPPLPBNr 4 RII:JPO dl0-250ld2I0f50-296) BBOWSS FERRY NUCLEAR PLANT In telephone conversationn between J. A. Damer, TVA, and !! ugh Dance, NHC, on January 19 and 20, 1981, we dieeuased the considerable dirriculty TVA was experiencing in mking opermble the Becwns Fcery contiruoun monitoring system (CMS) on the scram disch ege volume (SDV). In accordance with NRC IE Bulletin 80-17, Supplement 4, the CMS must be fully operable-on all three unite by January 21, 1981. The following is a sunmary of those conversations.

General. Electric Company (CE) field representatives have been assisting plant personnel in the installation. Two general probicas exist. First, the performanes of the systa in extremely senr.itive to transducer location en the SDV. The second in that the systea, as presently desi ced, suffers from a 5

high noise / low signal gain situation.

Durin8 the Browna Fcrry unit 3 refueling outage, technicians optimized the transduere location to enhance the system sensitivity. CF,further recommended electronic changea to improve the system performnee to the extent of being fully operable. We expect to receive the necessary parts from GE by January 30, 1981, and complete the mod Uications and testins described by the bulletin vithin three days thernpfter.

Following the unit 3 installation, Browns Ferr; units 1 and F will be modified as unit 3 and the te: ting repeated. We expect this to take approximstely one week. If the tr.3 ting indicate. that rurther optimir.ntion er the transducer location on units 1 and 2 it necessary, this wi'1 de cone at the next avalishic unit shutdown.

It should be esnphanized that the location of the transducer on the header 1r. extremely critical. We are concerned thr.t condi tions in the header arsy chanEn and t,egste opernbility of the system.

Operating experience will er.tcenina if this will occur.

i 1

8102030 W

A 6 " n.qu,7.r w.

. ? S. 'C?x,.. f.."!d%**C&fa.@RA2 X V,T

~=5f..'N 4y$;$nlQ$lh,YU,M, 5

r Y5{

  • i 7p.- #v O,5 M cs i

2vr-m 3 i

NW Zo# E. Mr. James P. O'Reilly Jenuisry 20, 1901 The above represents a best faith errnet on TVA's part and we will continue to do everything possible to rake tne Browas Fccry CMS rally operable.

If we enesunter additional unavojdable delaya in the CMS in.plement.:stien.sc%dule, we will notify your office promptly. Until TVA modirlas and tests the Eystm in acecrdance with Supplertent 4, the current 30-minute interval survoillance testing using the portable ultrasonic equipment will be continued.

7t is our understanding that our aDproach as stated above provides an acceptable basis for continued operation.

If you have any questions, please call Jim Dcaer at FTs 857-2010 Very truly yours, TENNESSEE VAI. LEY AUTHORI"T

/L J. L. Cross

  • ~

f,.!'..../.,, -

Exocutive Assistant to the Manager of Power

\\ [.Sh'*h ferd6 t " n'd subscribed berare me issy or Ger *.

ise, i

\\l.s

' A 7YL 8 l? W S

.M ete"y Public My Comission Expires k

ec b'.

Victor Stello, Director Offier of Inspection and Entercoment U.S. Nuciene Regulatory Ccmi~esion Watshingtcn, DC 20555