ML19290F013

From kanterella
Jump to navigation Jump to search
Interim Significant Deficiency Rept 80-01:TJ Cope QC Insp Program of Galvanized Cable Trays,Failed to Check for Burrs on Cable Tray Rungs.Caused by Failure to Adequately Inspect & Correct Tray After Galvanizing
ML19290F013
Person / Time
Site: Beaver Valley
Issue date: 03/10/1980
From:
DUQUESNE LIGHT CO.
To:
Shared Package
ML19290F010 List:
References
NUDOCS 8003170455
Download: ML19290F013 (1)


Text

INTERIM REPORT ON CABLE TRAY GALVANIZING DEFICIENCY f

AT BEAVER VALLEY POWER STATION - UNIT NO. 2 1.

SUMMARY

A number of protrusions in the cable bearing area of hot dip galvanized safety related cable tray have been found.

These protrusions are a result of runs and imperfections in the hot dip galvanizing which solidified to form spikes and sharp edges.

The cable tray vendor did not adequately inspect and correct tray after galvanizing as required by the purchase specification.

2.

IMMEDIATE ACTION TAKEN All uninstalled tray on site are being inspected for galvanizing projections prior to installation.

If projections are found, they are filed smooth.

Tray remaining to be shipped is being thoroughly inspected by the Duquesne Light Company inspectors to ensure no projections exist.

An audit of the quality control program is being performed to determine effectiveness.

The Nuclear Regulatory Commission was informed that the tray galvaniz-ing was potentially reportable under the provisions of 10CFR50.55 (e) (1) (i) on February 7, 1980 by Mr.

H.

A. Van Wassen of Duquesne Light Company.

3.

DEFICIENCY Duquesne Light Company inspectors had, over a period of time, found numerous rejectable pieces of tray which the cable tray vendor had presented for final inspection.

As a result, the inspectors issued a Nonconformance and Disposition Report iden-tifying that the vendor was not adequately inspecting tray.

Inspection of tray on site was performed and similar deficiencies were found.

4.

ANALYSIS OF SAFETY IMPLICATIONS Galvanizing deficiencies within the cable bearing area of the tray may have the potential to damage cable jacketing and insulation.

This could occur from cable being either pulled over or sitting on a sharp projection.

Safety related cable has either neoprene or hypalon jacketing and it is questionable as to whether jacketing could be damaged by the protrusions.

To determine possible damage testing has been conducted in which cable was dragged over pro-jections in a manner to create considerable downward force.

No significant damage to jacketing was found.

However, with these tests results alone we are not able to determine whether a safety implication exists.

Additional analysis is required; a final report will be submitted on or before May 1, 1980.

5.

CORRECTIVE ACTION TO REMEDY DEFICIENCY Immediate action of inspecting tray before installation will be continued until all tray are installed.

Duquesne inspectors will thoroughly inspect all tray until confidence in the vendor's inspection program has been developed.

All installed safety re-lated tray will be inspected and deficiencies will be corrected or tray replaced before cable is pulled, thus eliminating any safety hazard associated with this deficiency, 8 003170[pfjj[