Forwards Recommendations for Fire Protection Design Review, Items 3.1.5 & 3.1.2,re Water Suppression Sys & Fire Water Supply,Respectively.Items Should Be Accepted
ML19290E940
Person / Time
Site: Haddam Neck File:Connecticut Yankee Atomic Power Co icon.png
Issue date: 12/20/1979
From: Randy Hall
BROOKHAVEN NATIONAL LABORATORY
To: Fergusoon R
Office of Nuclear Reactor Regulation
References
NUDOCS 8003170355
Download: ML19290E940 (2)


Text

,

I3

~

~ '

-,T j

E BROOKHAVEN NATIONAL LABORATORY f 75"_

ASSOCIATED UNIVERSITIES, INC.

(_

m_

Upton, New York 11973 Depcrtmentof NuclearEnergy (516) 345 2362 December 20, 1979 tobert L. Ferguson r

Systems Branch U.

Nuclear Regulatory Commission Washington, D. C.

20555

Subject:

Haddam Neck Fire Protection Review

Dear Bob:

Attached are the Brookhaven National Laboratory recommendations for design review items 3.1.5 and 3.1.2.

Very truly yours, Robert E. Hall, Group Leader Reactor Engineering Analysis REH/ENi/sd Attachment cc:

R. Cerbone L. Derderian (w/ attach)

R. Hall W. Kato V. Panciera u

8003170 3%

HADDAM NECK Fire Protection Review Item 3.1.2 Fire Water Supply Sketch SK-CY-2 provides sufficient design details for the additional feed from the fire pump to the underground fire main. We recommend that this item be accepted. This acceptance completes the review of all the aster-1sked items under 3.1.2.

Item 3.1.5 Water Suppression System The October 9,1979 response from the utility provides sufficient design criteria for the sprinkler system to be installed in the auxiliary building corridor. The system has been designed to provide both area and cable tray protection. The design criteria is acceptable. With the submittal of this information, all items asterisked under 3.1.5 have been reviewed I,nd found satisfactory. We recommend the acceptance of item 3.1.5.

%