_

7J C l OUISIANA P O W E A & L 1 G H T! P O BOX 6000. NEW OALEANS. LOUISIANA 70174 142 CELAAONCE STREET

  • (504: 366-2345 UEuS$ SYS E January 31,1980
c. t meu.

Vcs 8Woosnth P-Joucuan LPL 13057 Q-3-A35.07 Mr. K. V. Seyfrit, Director, Region IV U. S. Nuclear Regulatory Commission Office of Inspection and Enforcement 611 Ryan Plaza Drive, Suite 1000 Arlington, Texas 76012

SUBJECT:

Waterford SES Unit 3 Docket No. 50-382 Potential Construction Deficiency Report Defective Top Cover Gaskets NAMCO EA-180 Limit Switches

Reference:

LPL 12566 dated November 3, 1979

Dear Mr. Seyfrit:

We have completed our review of the subject potential construction deficiency concerning the subject NAMCO EA-180 Limit Switches.

NAMCO has informed us that if these switches are in a continuous ambient temperature of 1750F or less, no action is necessary.

Since the normal ambient temperature in the Waterford 3 SES Reactor Containment Building is less than 175 F, we have determined that no problem exists and this will not be considered a reportable construction deficiency.

Yours very truly, D. L. Aswell DLA/TFG/grf cc:

Director Office of Inspection and Enforcement U. S. Nuclear Regulatory Commission Washington, D.C. 20555 Director Office of Management Information and Program Control U. S. Nuclear Regulatory Commission Washington, D.C.

20555 80 0317 00G/