Advises That IE Bulletin 80-03, Loss of Charcoal from Std Type II,Two-Inch,Tray Adsorber Cells, Was Sent to Listed Utils on 800206
ML19290E514
Person / Time
Issue date: 02/14/1980
From: Carroll D
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To: Wright G
ILLINOIS, STATE OF
References
NUDOCS 8003140149
Download: ML19290E514 (2)


Text

/

n atog

[e y

C(U[gg{ pILb6 o,

UNITED STATES 3

, -.,, (

g NUCLEAR REGULATORY COMMISSION r

REGION lli d6

[

799 ROOSEVELT ROAD e

o e

GLEN ELLYN,ILLINOls 60137

%.'.%/

fEB 14 \\%

State of Illinois Department of Public Health ATTN:

Mr. Gary N. Wright, Chief Division of Nuclear Safety 535 West Jefferson Street Springfield, IL 62761 Gentlemen:

The enclosed IE Bulletin No. 80-03 titled " Loss of Charcoal from Standard Type II, 2 Inch, Tray Absorber Cells" was sent to the following licensees on February 6,1980, for action.

American Electric Power Service Corporation Indiana and Michigan Power Company D. C. Cook 1, 2 (50-315, 50-316)

Cincinnati Gas & Electric Company Zimmer (50-358)

Cleveland Electric Illuminating Company Perry 1, 2 (50-440, 50-441)

Commonwealth Edison Company Braidwood 1, 2 (50-456, 50-457)

Byron 1, 2 (50-454, 50-455)

Dresden 1, 2, 3 (50-10, 50-237, 50-249)

La Salle 1, 2 (50-373, 50-374)

Quad-Cities 1, 2 (50-254, 50-265)

Zion 1, 2 (50-295, 50-304)

Consumers Power Company Big Rock Point (50-155)

Midland 1, 2 (50-329, 50-330)

Palisades (50-255)

Dairyland Power Cooperative LACBWR (50-409)

Detroit Edison Company Fermi 2 (50-341)

Illinois Power Company Clinton 1, 2 (50-461, 50-462) 8003140l@ #,

ni 1 % <-

State of Illinois '

Iowa Electric Light & Power Company Duane Arnold (50-331)

Northern Indiana Public Service Company Bailly (50-367)

Northern States Power Company Monticello (50-263)

Prairie Island 1, 2 (50-282, 50-306)

Public Service of Indiana Marble Hill 1, 2 (50-546, 50-547)

Toledo Edison Company Davis-Besse 1 (50-346)

Union Electric Company Callaway 1, 2 (50-483, 50-486)

Wisconsin Electric Power Company Point Beach 1, 2 (50-266, 50-301)

Wisconsin Public Service Corporation Kewaunee (50-305)

Sincerely, Dorothy E. Carroll, Acting Chief Administrative Branch

Enclosure:

IE Bulletin No. 80-03 cc w/ encl:

Mr. D. W. Kane, Sargent & Lundy Central Files Reproduction Unit NRC 20b Local PDR NSIC TIC RII i 1/jp 2/6/80

SSINS No.:

6820 UNITED STATES Accessions No.:

NUCLEAR REGULATORY COMMISSION 7912190669 0FFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.

20555 D

R 3 b{2 February 6, 1980 Jd c:-

I~

IE Bulletin No. 80-03 LOSS OF CHARCOAL FROM STANDARD TYPE II, 2 INCH, TRAY ADSORBER CELLS Description of Circumstances:

During preliminary leak tests of charcoal adsorber cells in certain ventilation systems at Sequoyah Nuclear Plant, it was determined that on certain adsorber cells the spacing between rivets securing the perforated screen to the casing was too great to ensure adequate contact between the casing and the screen, thus allowing charcoal to escape.

The problem was discovered when a visual inspection detected loose charcoal on the floor of the filter housings and on the outside horizontal r.urfaces of the adsorber cells. Loss of charcoal was alsa indicated by observation of light penetrating through the cells. Additional inspection revealed that the rivets securing the perforated screens to the cell casing were approximately six inches apart and the screen appeared to be sagging away from the casing between rivets.

The particular adsorber cells being tested at Sequoyah Nuclear Plant were Flanders Type II pre-1974 fabrication.

There is a possibility that design of adsorber cells with wide spacing between screen rivets may pass initial freon leak tests but degrade significantly during operation thus reducing the margin of safety during postulated accidents.

The responses from this Bulletin will be used by the NRC to evaluate need for more frequent inspection / testing.

For all power reactor facilities uith an Operating License:

1.

Determine if charcoal adsorber cells in use, or proposed for use, have the potential for a loss of charcoal incidental to handling, storage or use (as appropriate). Particular attention should be directed to examina-tion of a) rivet spacing resulting in separation of screen and cell housing and b) adsorber cell or filter housing deformation causing loss of charcoal and/or channelir.g. Either of these items could result in a degraded filtration system incapable of performing its intended function.

The preferred method of this determination is a visual inspection of the filter housing and adsorber cells as described in Section 5 of ANSI N510-1975. If this method is not feasible, state in the report required by Paragraph 4 how the determination was made.

2.

For ESF filtration systems, any identified defective cells shall be replaced and the operability of the system (af ter cell replacement)

IE Bulletin No. 80-03 February 6,1980 Page 2 of 2 demonstrated by leak testing within 7 days. Preferred method of leak testing is as described in Regulatory Guide 1.52 and Section 12 of ANSI N510-1975.

3.

For normal ventilation exhaust filtration systems which employ charcoal adsorber cells and for which radioactive removal efficiency has been assumed in determining compliance with the "as low as reasonably achievable" design criteria of 10 CFR 50, Appendix I, any identified defective cells shall be replaced as soon as possible but at least within 30 days. Af ter replacement, the system should be demonstrated operable by leak testing within an additional 30 days. Preferred method of testing is as described in Regulatory Guide 1.140 and Section 12 of ANSI N510-1975.

4.

Report in writing within 45 days of the date of this Bulletin the results of the determination required by Paragraph 1.

The report shall include the type of cells employed (manufacturer and cell design), system containing the cells, observed cell condition (degradation / sagging) and a discussion of visual inspection procedure and results.

For all Power Reactor Facilities with a Construction Permit:

1.

Visual inspection shall be conducted only if the charcoal adsorber cells have been purchased and shipment received. A representative number (approximately 5) of each type of cell design / manufacturer shall be visually inspected for such deficiencies as rivet spacing and screen / casing separation which could lead to loss of charcoal incidental to handling, storage, or use.

2.

Report in writing within 45 days of the date of this Bulletin the results of the inspection required by Paragraph 1.

The report shall include the type of cells (manufacturar and cell design), observed cell condition (degradation / sagging) and a discussion of the inspection procedure and results.

Reports shall be sent to the Director of the appropriate NRC Regional Office listed in Appendix D of 10 CFR 20 with a copy of the Director, Division of Fuel Facility and Materials Safety Inspection, Office of Inspection and En f orc ement, USNRC, Washington, D.C.

20555.

Approved by CAO, B18;225(R0072); clearance expires, 7/31/80.

Approval was given under a blanket clearance specifically for identified generic problems.

Enclosure:

List of Recently Isoued IE Bulletins

l IE Bulletin No. 80-03 Enclosure February 6,1980 RECENTLY ISSUED IE BULLETINS Bulletin Subject Date Issued Issued To No.

80-02 Inadequate Quality 1/21/80 All BWR licenses with Assurance for Nuclear a CP or OL 80-01 Operability of ADS Valve 1/11/80 All BWR power reactor Pneumatic Supply facilities with an OL 79-OlB Environmental Qualification 1/14/80 All power reactor of Class IE Equipment facilities with an OL 79-28 Possible Malfunction of 12/7/79 All power reactor Namco Model EA 180 Limit facilities with an Switches at Elevated OL or a CP Temperatures 79-27 Loss Of Non-Class-1-E 11/30/79 All power reactor Instrumentation and facilities holding Control Power System Bus OLs and to those During Operation nearing licensing 79-26 Boron Loss From BWR 11/20/79 All BWR power reactor Control Blades facilities with an OL 79-25 Failures of Westinghouse 11/2/79 All power reactor BFD Relays In Safety-Related facilities with an Systems OL or CP 79-17 Pipe Cracks In Stagnant 10/29/79 All PWR's with an (Rev. 1)

Borated Water System At OL and for information PWR Plants to other power reactors 79-24 Frozen Lines 9/27/79 All power reactor facilities which have either OLs or cps and are in the late stage of construction 79-23 Potential Failure of 9/12/79 All Power Reactor Emergency Diesel Facilities with an Generator Field Operating License or Exciter Transformer a construction permit