ML19290A098
| ML19290A098 | |
| Person / Time | |
|---|---|
| Site: | Crane |
| Issue date: | 04/13/1979 |
| From: | Brooks B BABCOCK & WILCOX CO. |
| To: | Suhrke K BABCOCK & WILCOX CO. |
| References | |
| TM-0951, TM-951, NUDOCS 7910010528 | |
| Download: ML19290A098 (3) | |
Text
.-
%-~-
I
\\-
l
. i. - 8,.
TMI DOCUMErrS Y
~OY
[
DOCUMENT NO:
~
COPY MADE ON OF DOCUMDIT PROVIDED BY METROPOLITAN. EDISON COMPANY. s Supervisor, Docment Control, NRC 8
W e
e m
~
/5f 2910010.b% E w -.e
.m--.
-~ww.m.
.e,_
.w-mew.,,
m ure%Tnuity-
~~
'-' - -- -~
q.yo IRANSNITTALTO:
' Yl>/
@ 6 L'.
ROGERS TRANSMITTAL !
ALSO TELECOPY TO:
8 R. WILSON TRAtlSMITTAL #
tso.if I
jT/ B&W TRAILER 26 TRANSMITTAL #-
W21S TIME 11:0S AM DATE APRIL 13, 1979 SUBJECT INFORMATION R5LATIVE TO 'C0tlTROL ROOM $VACUATIO'N-
~
KEN.ELLISON REQUEST APPROVED BY
411 '
OPERATI0ftS MAllAGER g.
e
~
9 e
e e
e e
O o
e l
9 e
O l'
e e
6 e
l 9
e e
o 9
dD e
2221 139 -
3
\\
~
e+*
~
~
BABC0CK & SI[C0X CUIIIAtIY ~
~
.. ~
~
444/ * ' ~" N
~
~
POWER' GENERATION GROUP j
- i. To l
ENGINEERING OPERATIONS MANAGER - K.E.'SUHRKE
~
g I
' rom PLANT DESIGN / SAFETY - B.L. BROOKS 1>.q s D 805 a e
File No.
Cu st.
- I or Ref.
}
Subj.
Date 0830 HOURS KEN ELLISON TELECON REGARDING SITE EVACUATION APRIL 13, 1979 gm,..,..........................;...a.
r THIS MEMO IS TO DOCUMENf THE INFORMATI0'N GIVEN TO KkN.ELLISON VIA TELECON AT 0630 ON APRIL 13, 1979.
KEN HAD REQUESTED INPUT ON MINIMUM MAKE-UP FLOW SHOULD TMI BE FORCED INTO CONTINGENCY PROCEDURE C-26 ON SITE EVAUCATION.
PROCEDURE C-26 BASICALLY CALLS
~
FOR MINIMUM MAKE-UP FLOW TO SLOWLY TAKE THE RCS TO A SOLID CONDITION WITH DH AS A BACK-UP (AUTOMATICALLf' INITIATE AT AN RCS PRESSURE OF'
~
200'PSIG).
THE INFORMATION PASSED ON TO KEN WAS AS FOLLOWS:
INITIAL PRESSURIZER LEVEL OF 200" ASSUMPTIONS:
INITIAL PRESSURIZER TEMPERATURE OF S50 E
.s 19 GPM SEAL INJECTION FLOW 3 GPM SEAL RETURN FLOW (NOTE: C-26 CALLS FOR ISOLATION OF SEAL RETURN BUT LEAVES THE RCP RUNNING SEAL RETURN MUST BE MAINTAINED)
PRESSURIZER C00LDOWN TO 230 F IN APPROXIMATELY
~
~ Q j
.14 0 S HOURS ~
2 GPM RCS L'EAKAGE LETOOWN ISOLATED (REQUIRED IN C-26) s GIVEN THESE ASSUMPTIONS, HAND CALCULATIONS SHOWED THE FOLLOWING RESULTS:
\\
APPROXIMATELY S-GPM MAKE-UP FLOW REQUIRED I
(
- ,"f
- ~..Q I
TO MAKE-UP FOR CONTRACTION VOLUME IN
.I PRESSURIZER i
- 19 GPM FDL INJECTION FLOW RATE MORE THAN ADEQUATE T,0 ALLOW FOR SEAL RETURN, RCS LEhKAGE, AND CONTRACTION AND STILL TAKE
~ RCS SOLIO IN LESS THAN 13 HOURS..
}
CALCULATIONSWERENOTGIVNTOKEtELLISONBUTAREATTAbHEDFOR
~
~
YOUR INFORMATION.
ASSUME:
19 GPM SEAL INJECTION
~
3 GPM SEAL RETURN
~
2 GPM RCS LEAKAGE PRESSURIZER C00LDOWN.550 F - 230 F IN a
/
I 5 HOURS f
~
CALCULATE MAKE-UP REQUIRED FOR CONTRACTIM VOLUME (ALL NUMBERS FOR R. WINKS):
- SPECIFIC VOLUME O 550 F =.02176; O 230 F =.01685
- 0 200" PRESSURIZER WATER VOLUME = 825 FT.3
- LBM. WATER 0 550 F = 825 FT.3/.02176 FT.3/LBM = 37,900 LBM.,
- VOLUME 0'230 F = 37,900 LBM. X.01685 FT.3/LBM. = 639 FT.3
- CONTRACTION VOLUME = 825 FT.3 - 639 FT.3 = 186 FT.3
- 186 FT.3 y 7.48 GALLONS /FT.3 = 1400 GALLONS
- 1400 GALLONS /5 HOURS = :i GPM EXCESS MAKE-UP = 19 GPM (SEAL INJECTION).- 3 GPM (SEAL RETURN -
2 GPM (LEAKAGE) - SGPM (CONTRACTION = 9 GPM
~
S-2221 141 s
TIME TO GO SOLID:
\\
- 6730 GALLONS NEEDED TO GO SOLI (FROM 200")
~..
g
- 9 GPM X 5 HOURS X 60 MIti/HR = 2700 GALLONS t-
- AFTER 5 HOURS ASSUME NO CONTRACTION (PRESSURIZER @ 230'F)
I THEREFORE,.14 GPM EXCESS
.I T
GALLONS
- 6730 - 2700 =.4030
~
- 4030 GALLONS /14 GPM = 288 MINUTES = 5 HOURS
- TOTAL '= 10 HOURS TO GO SOLID l
13 HOURS GIVEN TO KEN ELLISON TO ALLOW FOR USE OF APPROXIMAT.ES.