Consumels power Company

( r.,

q u'l General Offices
212 West Michigan Avenue, Jackson, Michigan 49201 e Area Code 517788-0550 June 5, 1979 Director, Nuclear Reactor Regulation Att Mr Dennis L Ziemann, Chief Operating Reactors 3 ranch No 2 US Nuclear Regulatory Co==ission Washington, DC 20555 DOCKET 50-255 - LICENSE DPR-2G -

PALISADES PLAUT - AUXILIARY FEED-WATER SYSTDI OPERA 3ILITY In response to concerns regarding the TMI incident, Consumers Power Company will co==it to operation of the auxilury feedvater system in the following manner:

With the primary coolant system temperature greater than 325, both auxiliary feedvater pumps and one fire pump will be crerable except as folleva:

a.

One auxiliary feecater pump may be inoperable for a period of 72 ho rs.

b.

The firevater cakeup to the auxiliary feedvater pump suction may be inoperable for a period of 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />.

If an inoperable auxiliary feedvater pump is not restored to service in 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />, the plant vill be placed in hot shutdown within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.

This mode of operation vill be incorporated in the plant operating procedures by June 15, 1979, and vill continue in effect until such time as Auxiliary Feedvater Technical Specification Changes have been approved.

David P Hoffman (Signed) 2231 002 David P Ecffman Assistant Nuclear Licensing Administrator CC JGKeppler, USHRC

[

7 06110/ 6 4