bec to DAC:ADft:

CENTRAL FILES 1

POR:HQ j

LPDR i

W NSIC ARKANSAS POWER & LIGHT COMPANY STATE POST OFRCE BOX 551 LITTLE ROCK. ARKANSAS 72203 (501) 371-4000 November 29, 1979 1-119-20 Mr. K. V. Seyfrit, Director Office of Inspection & Enforcement U. S. Nuclear Regulatory Commission Region IV 611 Ryan Plaza Drive, Suite 1000 Arlington, Texas 76011

Subject:

Arkansas Nuclear One - Unit 1 Docket No. 50-313 License No. DPR-51 IE Bulletin 79-13 (File:

1510)

Gentlemen:

The following is provided in response to Item 2 of IE Bulletin 79-13, Revision 2:

1.

Arkansas Nuclear One - Unit I utilizes three different feedwater systems.

Auxiliary and main feedwater feed the steam generators through shared spargers while the emergency feedwater feeds through spargers used by that system only.

2.

We will not perform the inspections required by Item 2(b) for the following reasons.

In all cases where auxiliary feedwater injection is used it is preheated.

Emergency feedwater is not used to maintain steam generator level during any normal operating mode.

3.

The inspections required by Item 2(c) were performed as part of the effort required for IE Bulletins 79-02 and 79-14.

Any discrepancies found will be reported as required by them.

Very truly yours, bW(. f&n David C. Trimble fianager, Licensing DCT:f10W:pw cc: Mr. Norman C. Mose'y, Director Mr. W. 3. Johnson Div. of Reactor Operations Inspection U.S. Nuclear Regulatory Commission Nuclear Regulatory Commission P. O. Box 2090 4350 East West Highway Russellville, Arkansas 72801 Bethesda, Maryland 20555 MEMOEA MICOLE SOUTH UT1UT:E3 SYSTEM