In Response to NRC ,Forwards Suggestions Re Ground Water Monitoring & Waste Water Lagoon.Water Supply Well & Reaffinate Ponds Should Be Sampled Monthly.All above-ground Lagoons Should Be Eliminated as Soon as Possible
ML19282C056
Person / Time
Site: Wood River Junction
Issue date: 02/01/1979
From: Dan Warner
DON L. WARNER, INC.
To: Crow W
NRC OFFICE OF NUCLEAR MATERIAL SAFETY & SAFEGUARDS (NMSS)
References
NUDOCS 7903200127
Download: ML19282C056 (1)


Text

.....

-\\.

DON 1 WARNER f-"'"

y

e. o. mox,av

,Q:-

V nom, uVsseum.s4oi

,g v.

N,e f

3 February 1, 197,9 0

;.a -

r.

. h,

'.?

q '.

~

g Mr. W. T. Crow, Section Leader

~ '

-DV

,..e Uranium Fuel Fabrication Section Fuel Processing and Fabrication

(

of Fuel Cycle 2r.d Di s Material Safety U.S. iluclear Regulatory Commission g g00M1 Washington, D.C.

20555 M

Dear Mr. Crow:

I have delayed responding to your letter of flovember 9, as I have been discussing the nature of my response with Dr. Shum of your My suggestions regarding grcund water monitoring and waste water lagoon design at the United Nuclear Corporation Rhode Island office.

1 plant are as follows.

I believe that sampling of the monitor wells monthly is desirable.

tionitor well samples should be analyzed for gross alpha and gross beta.

If the gross alpha value exceeds 15 pc/l or the gross beta value ex-ceeds 50 pc/1, then the water should be analyzed for the specific The nonradicactive parameters that should radioactive elements present.

If nitrate be analyzed for are pH, nitrate and nitrite, and fluoride.and analyzed for cadmium, mercury, nickel, and zinc.

- The water supply well shoUld be' sampled monthly and-the same tests.

' ~ : * =~. ; -

i

~

run as recommended above, except that the heavy metal analyses should j

be performed regardless of the nitrogen value.

j The raffinate ponds should be sampled mcathly in such a way that Pond the sample is as representative as possible of the entire pond.

samples should be analyzed as described above for. the water supply well 7

samples.

- - - ~ ~.. - - - -

Uf4C's proposed above-ground lagocn design apifears to~be sith factory;

~

~

h6 wever, as I have recommended in-the past, all. of. the lagoons should be eliminated at the earliest possible time and-an appropriate waste t'reat-ment process adopted.

Sincerely yours, Ycuv =

u-~

2n L. Narner Cor.sulting Geological e-y Enc.ineer 7903200127