Forwards LERs 79-013/03L-0,79-014/03L-0 & 79-012/03L-0
Date released: 10/23/2019 Download: ML19282A780


LER 79-012/03L-0 on 790127:core Protection Computer Channel B Failed,Resulting in Trips.Caused by Analog High Level Amplifier Card Improperly Seating in Connector.Card Reseated & Functional Test Conducted
ML19282A787
Person / Time
Site: Arkansas Nuclear 
Issue date: 02/26/1979
From: Shively C
ARKANSAS POWER & LIGHT CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
Download: ML19282A787 (1)
LER 79-014/03-0 on 790127:plant Protection Sys C Containment Bldg Pressure Transmitter 2PT-5603-3N Failed, Causing Hi & Hi-Hi Containment Pressure Trips.Caused by Loose Output Connection,Which Was Subsequently Reconnected
ML19282A782
Person / Time
Site: Arkansas Nuclear 
Issue date: 02/26/1979
From: Shively C
ARKANSAS POWER & LIGHT CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
Download: ML19282A782 (1)
LER 79-013/03L-0 on 790127:control Element Assembly Cluster (Ceac) Deviation Alarms Received.Caused by Disturbance of Ceac Cable Connections
ML19282A781
Person / Time
Site: Arkansas Nuclear 
Issue date: 02/26/1979
From: Shively C
ARKANSAS POWER & LIGHT CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
Download: ML19282A781 (1)
Forwards LERs 79-013/03L-0,79-014/03L-0 & 79-012/03L-0
ML19282A779
Person / Time
Site: Arkansas Nuclear 
Issue date: 02/26/1979
From: Rueter D
ARKANSAS POWER & LIGHT CO.
To: SEYFRIT K V
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
Download: ML19282A779 (1)