ML19276H148

From kanterella
Jump to navigation Jump to search
Responds to NRC Re Violations Noted in IE Insp Rept 50-289/76-19.Corrective Actions:Radiation Areas Posted in Accordance W/Surveys&Training Re Administrative Procedure 1013 to Be Completed 761101
ML19276H148
Person / Time
Site: Crane 
Issue date: 09/12/1976
From: Arnold R
METROPOLITAN EDISON CO.
To: Brunner E
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML19276H147 List:
References
760921, GQL-1318, NUDOCS 7910150076
Download: ML19276H148 (3)


Text

W.-

/

M c,,,,

=,

/

SU3SIDIARY OF GENERAL PUBUC UHUHE METROPOLITAN EDISON COMPAN POST OFFICE BOX 542 READING, PENNSYLVANI A 19G03 TELEPHONE 215 - 929-3601 September 21, 1976 GQL 1318 Mr. Eldon J. Brunner, Chief Reactor Operations & Nuclear Support Branch U. S. Nuclear Regulator /' Commission 631 Park Avenue King of Prussia, PA 19406

Dear Mr. Brunner:

Docket No. 50-289 Operation License No. DPR-50 Three Mile Island Nuclear Station, Unit 1 (TMI-1)

Inspection Report No. 50-289/76-19

()

This letter and the attached enclosure are in respcnse to your inspection letter of August 2,1976, concerning Mr. W. Ruhlman's inspection of T'4I-1 and the resultant finding of an apparent viclation.

This is bei'ig cubmitted late pursuant to the September 17, 1976 telephone conversation between Mr. Ruhlman and our Mr. Y. E. Potts.

Sincerely, R. C. Arnold Vice President RCA:JJM:daf Enclosure 1413 045 01 7910150 1

7b

W m

Metropolitan Edison Company J

Three Mile Island Nuclear Station Unit 1 (TMI-1)

Docket No. 50-289 License No. DPR-50 Inspection No. 76-19 RESPONSE TO DESCRIPTION OF APPARENT VIOLATION APPARENT VIOLATION A 10 CFR 20.203 (b) states: " Radiation areas. Each radiation area shall be conspicuously posted with a sign or signs bearing the radiation caution symbol and the vords: CAUTICH RADIATION ARZA."

Health Physics Procedure 1610, ESTABLISHING AND POSTING AREAS, Revision 4, dated July 28, 1976,-

Paragraph 5.1.2 states: " ' Radiation Areas' vill be posted with caution signs, acceptable to the AEC, that read: ' Caution' RADIATION AREA."

Contrary to the above, the radiation area at the entrance to the Drum Storage Area near the 1 CES Switchboard was posted as a High Radiation Area when, in fact, it was a Radiation Area.

Prior to the completion of the inspection, the area was surveyed, verified as a Radiation Area, and the posting was changed to reflect the actual conditions. This corrective action was verified by the inspecter.

RESPCNSE TO APPARENT VICLATION A In the future, Met-Ed vill not make a practice of posting as "High Radiation Areas" areas whose radiation levels vary between those constituting a "High Radiation Area" and those constituting a " Radiation Area".

Such areas vill be posted as surveys indicate, and care vill be taken to insure that posting is changed as required when the factors affecting the radiation level of the area are changed.

APPARENT VIOIATICN B Technical Specification 6.8.1 states in part: " Written procedures and administrative policies shall be established, implemented and maintained..."

Unit 1 Administrative Procedure AP 1013, BYPASSING OF SAFETY FUNCTIONS AND-JUMPER CONTROL, Revision 3, dated July 17, 1974, Paragraph D.2.e, states in part: "Whenever the leads are replaced the following information shall be en-tered in the log: Date-Time-Replaced By."

Contrary to the above, Administrative Procedure 1013 was not implemented in that two leads, controlled by lifted lead tags #27 and #28, had been replaced without filling in the required information in the log.

This item was identified and documented by the licensee on NCR TMI 76-372.

However, corrective actions to prevent recurrence were neither defined nor implemented nor was this specific deficiency corrected. Therefore, a response to this item is required. Your response should address also those actions you plan to take to ensure that operating staff are informed pronptly of deficiencies identified through internal audits and surveillance.

1413 046

RESEONSE TO APPAREUT VIOLATION B The cause of this deficiency was determit.ed to be personnel being unfamiliar with the requirements of Procedure AP 101",.

To correct this, all Maintenance Department personnel whose work could in"olve lifting leads or placing jumpers vill be trained or retrained in t..e requirements and responsibilities imposed by Administrative Procedure 1013. This training vill be completed by 1 November 1976.

The time taken to correct the condition identified by the Internal audit was excessive.

The Supervisor of Operations will assure prompt action is taken to correct those deficiencies.

The NCR #76-372 action was completed on 13 August 1976 and the NCR officially closed out on 27 August 1976.

We are now in compliance.

~,

s

,)

!413 047