ML19276D983

From kanterella
Jump to navigation Jump to search
Notice of Violation from Insp on 781113-16
ML19276D983
Person / Time
Site: Vermont Yankee File:NorthStar Vermont Yankee icon.png
Issue date: 12/11/1978
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To:
Shared Package
ML19276D975 List:
References
50-271-78-25, NUDOCS 7903020062
Download: ML19276D983 (1)


Text

.

APPENDIX A NOTICE OF VIOLATION Vermont Nuclear Power Corporation Docket No. 50-271 Westborough, Massachusetts Based on the results of the NRC inspection conducted on November 13-16, 1978, it appears that certain of your activities were not conducted in full compliance with the NRC regulations and the conditions of your NRC Facility License No. DPR-28. These items are categorized as Deficiencies.

A.

Section 1.B.2 of the Nonradiological Technical Specifications (NRTS) requires, in part, that the total residual chlorine con-centration at the aerating structure be limited to 0.5 mg/1.

Contrary to this requirement, on October 20, 1978, the total residual chlorine concentration at the aerating structure was 1.1 mg/1.

B.

Section 1.B.3 of the NRTS requires that the hydrogen ion concentra-tion (pH) of plant discharges shall be controlled within pH limits of 6.5 - 8.5 except when due to natural causes.

Contrary to this requirement, on April 29, 1978, the plant discharge pH was 8.8, while the river maximum pH during this day was 7.4.

0 79030200