ML19274E991

From kanterella
Jump to navigation Jump to search
Requests Review of Possibility of Requiring Banks of Pressurizer Heaters to Be Classified as Safety Sys
ML19274E991
Person / Time
Site: Midland
Issue date: 05/29/1979
From: Lainas G
Office of Nuclear Reactor Regulation
To: Check P
Office of Nuclear Reactor Regulation
References
NUDOCS 7906070077
Download: ML19274E991 (2)


Text

.

f arc UNITED STATES

,' g f.

NUCLEAR REGULATORY COMMISSION y

p, WASHINGTON, D. C. 20555 jj k *.... /

MAY 2 91919 MEMORANDUM FOR:

P. Check, Chief, Reactor Safety Branch, Division of Operating Reactors FROM:

G. Lainas, Chief, Plant Systems Branch, Division of Operating Reactors

SUBJECT:

REQUIRING PRESSURIZER HEATERS AND CONTROLS TO BE SAFETY GRADE In response to a note from V. Stello concerning the issue of safety system classification for pressurizer heaters, we contacted the Project Manager for the licensing of the Midland Nuclear Plant who informed us that the applicant, Consumers Power Company, will require that two of the six banks of pressurizer heaters be qualified as safety grade equipment.

The design basis for the Midlant Plant requires that following an anticipated transient, i.e., loss of offsite power, the plant achieve and maintain indefinitely hot shutdown condition.

The Midland design does not incorporate the ability to take the plant to a cold shutdown condition using only safety grade equipment.

Qualifying two banks of pressurizer heaters as safety grade will require that the: (1) heaters be seismically qualified, (2) heater banks have a redundant Class IE control systems, (3) heater bank controls are energized from Class IE power sources, and (4) design satisfy the requirements of IEEE Std. 279-1971 and heaters be energized from a Class IE power system that satisfies the r :quirements of IEEE Std. 308-1974.

The DSS position at this time is to require that the Midland design satisfy the above cited requirements for safety grade equipment.

In view of the fact that this issue is a recent development, DSS has not extended this position, at this time, to all future plants to be licensed.

It is concluded from correspondence between the Midland applicant and the NSSS manufacturer (B&W) that B&W does not believe that the pressurizer heaters are components of a safety system; and therefore, do not have to satisfy Class IE qualification requirements. A cursory review of the other two PWR manufacturers, indicates that the pressurizer heaters are normally used to bring the plant to safe shutdown following an anticipated transient, but no credit is taken for these units and they are not presently considered as safety grade equipment.

TD00070077

(gC POe

- The issue of requiring a selected number of banks of pressurizer heaters along with their controls, certain instrumentation and power supplies to be upgraded to the status of safety grade equipment is brought to your attention to consider its application to operating plants. There fore, it is requested that you review the issue and determine whether or not certain banks of pressurizer heaters be classified as safety systems, bN 6

G.Lainas, Chief (

Plant Systems Branch Division of Operating Reactors

Contact:

J. Burdoin, X28077 cc:

V. Stello D. Eisenhut R. Vollmer B. Grimes W. Russell J. Carter F. Rosa R. Satterfield M. Srinivasan G. Lainas D. Tondi J. Burdoin