ARKANSAS POWER & LIGHT COMPANY POST OFFICE BOX 551 LITTLE ROCK. ARKANSAS 72203 [501)371 4000 February 2, 1979 2-029-3 Director of Nuclear Reactor Regulation ATTN: !!r. J. F. Stolz, Chief Light Water Reactors Branch #1 U. S. Nuclear Regulatory Commission i

Washington, D. C. 20555

Subject:

Arkansas Nuclear One-Unit 2 Docket No. 50-368 License No NPF-6 Low Steam Generator Water Level Setpoint (File: 2-1511.1)

Gentlemen:

As discussed with your Mr. L. Engic in a meeting on January 30, 1979, the following supplemental information to our January 9, 1979, Technical Specification Change Request is provided.

The setpoint for Steam Generator Water Level Low is 45% indication.

To that value the appropriate errors were added (4.4*6) fo_ the old Fischer S Porter transmitter to arrive at the existing Technical Specification setpoint of 49.4%.

The corresponding errors associated with the Rosemount transmitter equal 1.5"6 which added to 45", yields the proposed Technical Specification setpoint of 46.5"..

Very truly yours, M,,.

-te Daniel H. Williams Manager, Licensing Di!W:JTE:1g gool/s 790213 o/M MEMPEF1 M100LE SOUTH UTILITIES SYSTEM