ML19269D424

From kanterella
Jump to navigation Jump to search
Responds to IE Bulletin 79-04 Re Weights of Swing Check Valves.Forwards List of Piping Sys Where Valves Are Installed.Results of Review to Be Provided When Available
ML19269D424
Person / Time
Site: Point Beach  NextEra Energy icon.png
Issue date: 05/02/1979
From: Burstein S
WISCONSIN ELECTRIC POWER CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
NUDOCS 7906040027
Download: ML19269D424 (3)


Text

3L k

WISCONSIN Electnc eom coumr 231 W. MICHIGA'd, P.0 BOX 2046 MILWAUKEE. nl 53201 May 2, 1979 Mr. James G. Keppler, Director Office of Inspection and Enforcement, Region III U. S. NUCLEAR REGULATORY COMMISSION 799 Roosevelt Road Glen Ellyn, Illinois 60137

Dear Mr. Keppler:

D0CKET N05. 50-266 AND 50-301 P0lf4T BEACH NUCLEAR PLAf4T RESPONSE TO IE BULLETIN NO. 79-04 This is to respond to IE Bulletin No. 79-04 which requested informa-tion concerning weights of swing check valves used in Seismic Category 1 piping system stress analyses. These valves were provided by Velan Engineering Corporation and have a flange rating of 1500 psi.

We have reviewed our records for Point Beach Nuclear Plant and have detemined that 3-inch and 6-inch Velan check valves were used in the Chemical and Volume Control System and the Safety Injection System. A list of the piping systems in which these valves are installed, as requested by Item 1 of IE Bulletin No. 79-04, is provided in the enclosure to this letter. We have also determined that valve weights less than those given in your bulletin were used in piping system analysis. We are presently reviewing the piping system stress analyses for the items noted in the enclosure and expect that this review will be completed in approximately two weeks.

Based upon a preliminary review, we do not expect that modificatiors will be required in either piping systems or piping supports. We will provide results of the review and the computer codes used, as requested by Items 4 and 5 of IE Bulletin No. 79-03 when they become available.

Should you have questions concerning this response, please contact me.

Very truly yours,

...j.--..

gse

/

Sol Burstein Executive Vice President 790604OODT Enclosure X3 1979 2258 141

Page 1 of 2 p'

I'0 INT BEACll UIIIT 1 VELA!! E!4Gil4LLRIr4G CORPORATI0rt VALVE LIST 1500 PSI AflSi RATING)

WEIGHT - LBS.

ACTUAL ORIGir4AL VALVE VELAri VALVE BULLETIN WEIGHT VELAN SYSTEM LINE NO.

ID DRAWING SIZE 79-04 USED DRAWING REMARKS Charging Line to Loop A 3-RC-250lR-12 295 78409 3"

85 82.5 60 No re-analysis required.

Cold Leg Charging Pump Discharge to 3 CH-2502R-3 370 78409 3"

85 75 60 Regenerative Heat Exchanger Residual Heat Removal Heat 6-SI-2501R-4 853A 78704 6"

450 360 225 Exchanger to Resctor 853C 78704 6"

450 350 225 Pressure Vessel Residual Heat Removal Heat 6-SI-250lR-5 853D 78704 6"

450 350 225 Exchanger to Reactor Pressure Vessel Reactor Pressure Vessel 6-SI-601R-2 853B 78704 6"

J.50 460 225 No re-analysis required.

Safety Injection Line Hot leg Loop B Injection 6RC-250lR-6 877A 78704 6"

450 366 225 Hot Leg Loop B Injection 6RC-250lR-9 877A 78704 6"

450 366 225 Safety Injection Pump 6SI-150lR-1 899A 78704 6"

450 300 225 Discharge to Injection 8990 78704 6"

450 300 225 Line N

N LD CO 4

N

Page 2 of 2 POINT BEACil UNIT 2 VELAN Ef4GIl4ETk'If4G CORPORATION VALVE LIST 1500 PSI NISI RATING)

WEIGHT - LBS.

ACTUAL ORIGIlML VALVE VELAN VALVE BULLETIN WEIGHT VELAN SYSTEM LINE NO.

ID DRAWING SIZE 79-04

__USED

_ DRAWING REMARKS Charging Line to Loop A 3-RC-250lR-12 295 78409 3"

85 66 60 Cold Leg Charging Purnp Discharge 3-CH-2502R-3 370 78409 3"

85 75 60 to Regenerative Heat Exchanger Residual Heat Removal 6-SI-250lR-4 853A 78704 6"

450 200 225 Heat Exchanger to 853C 78704 6"

450 200 225 Reactor Pressure Vessel Residual Heat Removal 6-SI-250lR-5 853D 78704 6"

450 366 225 Heat Exchanger to Reactor Pressure Vessel Reactor Pressure Vessel 6-SI-60lR-2 853B 78704 6"

450 366 225 Safety Injection Line Hot Leg Loop B Injection 6RC-250lR-6 877A 78704 6"

450 366 225 Hot Leg Loop B Injection 6RC-250lR-9 877A 78704 6"

450 366 225 Safety Injection Pump 6SI-150lR-1 899A 78704 6"

450 300 225 Discharge to Injection 8998 78704 6"

450 300 225 Line N

N LD Q

4 LA