Text
TENNESSEE VALLEY AUTHORITY CHATTANOOGA. TENNESSEE 374o1 500C Chestnut Street Tower II FEB 1 11979 Director of Nuclear Reactor Regulation Attention:
Mr.
S. A. Varga, Chief Light Water Reactors Branch No. 4 Division of Project Management U.S. Nuclear Regulatory Commission Washington, DC 20555
Dear Mr. Varga:
In the Matter of the Application of
)
Docket Nos. 50-327 Tennessee Valley Authority
)
50-328 Enclosed is TVA's response to question 3 transmitted by your J etter to N. B. Hughes dated December 8, 1978.
This question requested a listi1g of all Sequoyah Nuclear Plant (SNP) Class lE safety-related equipment with an identification of the basis for qualification.
This response will be incorporated into Amendment 60 of the SNP Final Safety Analysis Report.
Very truly yours,
".' /_
y vi
/f1
/
{ {it+ ? J
,hJ.
E. Cilleland Assistant Manager of Power Enclosure
\\
\\
790223004o An Equal Opportunity Employer
Q 7.60 Provide for our review a listing of all Class IE safety-(ICSB related equipment supplied by Westinghouse through their Q"3."-12/8/78) scope of supply.
This shall include all equipment located both inside and outside of containment.
It shall include, but not be limited to, sensors, signal-handling equipment, logic, switchgear, busses, inverters, instruments, motor operators, motor control centers,,2mps, relay racks and instrument racks.
In particular, the equipment located inside containment that is required to function during and subsequent to a steam line break event inside containment shall be identified.
Where more than one item of a given type has been supplied, it is only necessary to list the type and number supplied, and to present the required information for one representative item of that type.
The information supplied for each type shall include:
(a) Description of item including type or model number, (b) usage in the plant, (c) identification of the topical reports in which the qualification was described for both the seismic and environmental qualification and (d) the IEEE and other standards on which the qualification was based.
RESPONSE
Table Q 7.60-1 supplies the requested list.
W
Te51e Q 7.60-1 WESTINGHOUSE NSSS SUPPLIED 1E SAFETY-RELATED ELECTRICAL EQUIPMENT (SEQUOYAH - IN-CONTAINMENT)
FUNCTION (S)
QUAL. REFERENCE QUAL. REFERENCE CATEGORY EQUIPMENT MODEL PERFORMED IEEE-323-1971 IEEE-344-1971 Instrumentation Narrow Range RTD's Rosemount 176 KF RCS By-Pass Loop WCAP 9157 WCAP 8234 A (1b)"
Coolant Temperature Detection Wide Rn.ge RTD's Rosemount 176 KS RCS Main Loop Coolant WCAP 9157 W Test Report n/,
(8)
Temperature Detection Differential Pressure Barton 764 Monitor: RC Flow Rate NS-TMA-1950 NS-TMA-1950 Transmitters (23)
Pressurizer Level Steam Gen. Level Steam Flow Foxboro E 1301I RC Flow N/A WCAP 7817 & 854 (12)
Pressure Transmitters Barton 763 Monitor Pressurizer Pressure NS-TMA-1950 NS-TMA-1950 (6)
RCS Pressure Power Range Neutron Westinghouse Provide Feedback on N/A W Test Report 1/,
Det.ector Neutron Flux Density ifea te rs Hydrogen Recombiner Westinghouse Maintain Safe Containment WCAP 7820 WCAP 7820 Hydrogen Concentration Supp. 1-4 Supp. I Valve Operators Gate Valve Motor Limitorque Activate Safety Related WCAP 7744 b
Operators (6)
Motor Operated Gate Valves NS-CE-692 US-CE-756 Globe Valve Solenoid ASCO Regulated Air Supply to NS-CE-755 c
Air Operators (10)
Air Operated Safety Related Globe Valves
Table Q 7.60-1 (Continued)
WESTINGHOUSE NSSS SUPPLIED 1E SAFETY-RELATED ELECTRICAL EQUIPME!T (SEQUOYAll - IN-CONTAINMENT)
FUNCTION (S)
TJAL. REFERENCE QUAL. REFERENCl CATEGORY EQUIPMENT MODEL PERFORMED IEEE-323-1971 IEEE-344-1971 Diaphram Valve Solenoid ASCO Regulate Air Supply to NS-CE-755 c
Air Operators (3)
Air Operated Safety Related Diaphram Valves Gate Valve Solenoid ASCO Regulate Air Supply to NS-CE-755 c
Air Operators (2)
Air Operated Safety Related Gate Valves Instrumentation Pressure Transmitter Foxboro 611GM Monitor: Steam Pressure N/A WCAP 7817 &
(18)
Containment Supp. 8 Pressure WCAP 2541 1st Stage r
Turbine Pressure Differential Pressure Foxboro 613DM Monitor Feed Water N/A WCAP 7817 Transmittal (8)
Flow Rate WCAP 8541 Panel Mounted IIydrogen Recombiner Westinghouse Control of Hydrogen N/A WCAP 7820 &
Logic and Control Panel Recombiner Supp. 7 Swit ch;; ear Equipment Process Control Foxboro Monitor Operating Parameters, N/A WCAP 7817 Cabinets Initiate Reactor Trip and Safeguards Actuation Signals Solid State Protection Westinghvuse Initiate Reactor Protection N/A WCAP 7817 System Functions Supp. 2 & 3 Nuclear Protection Westinghouse Initiate Indicating Control, N/A WCAP 7817 System and Alarm Signals for Reactor Supp. 2 Control and Protection WCAP 8830 Reactor Trip Switchgear Westinghouse N/A WCAP 7817 Type DB Supp. 6
Table Q 7.60-1 (Continued)
WESTINGHOUSE NSSS SUPPLIED 1E SAFETY-RELATED ELECTRICAL EQUIPMENT (SEQUOYAH - IN-CONTAINMENT)
FUNCTION (S)
QUAL. REFERENCE QUAL. REFERENC CATEGORY EQUIPMENT MODEL PERFORMED IEEE-323-1971 IEEE-344-1971 Safeguards Test Cabinet Westinghouse Verify Safeguards N/A WCAP 7817 Integrity Supp. 7 Valve Operators Globe Valve Motor Limitorque Actuate Safety Related N/A b
Operators (6)
Motor Operated Globe Valves Gate Valve Motor Limitorque Actuate Safety Related N/A b
Operators (40)
Motor Operated Gate Valves Diaphram Valve Solenoid ASCO Regulate Air Supply to N/A c
Air Operators (7)
Air Operated Diaphram Valves t
Glove Valve Solenoid ASCO Regulate Air Supply to N/A c
Air Operators (9)
Air Operated Gate Valves Pump Motors Centrifugal Chargi;.g Westinghouse Charge RC Pumps, N/A d
(Hi-Head S.I.)
(2)
Emergency Care Cooling Safety Inje-tion Westinghouse Emergency Care Cooling N/A d
(2)
Residual Heat Removal Westinghouse Supply Constant Flow Through N/A d
(Low Head S.I.)
(2)
Residual Heat Exchangers, Emergency Care Cooling a Numbers in parentheses indicate the number of that item supplied by kestinghouse (if greater than 1).
b Seismic Tests performed for Limitroque by Lockheed Electronics Corporation.
These are 2786-3-4786 (2/6/73);
2786-4786 Issue 2 (9/5/72); 2773C-4773 (5/3/72)s and 2785-4-4785 (2/1/73).
c Seismic testing was performed by ASCO, a letter summarizing the results has been provided to Westinghouse PWR-SD.
d Seismic analysis of the pump motor structural assembly to demonstrate structural integrity was conducted by the vendor.
A copy of the reports is retained by Westinghouse PWR-SD.