ML19263B319

From kanterella
Jump to navigation Jump to search
Notice of Violation from Insp on 781003-05
ML19263B319
Person / Time
Site: Hartsville  
Issue date: 11/21/1978
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML17054C975 List:
References
50-518-78-12, 50-519-78-12, 50-520-78-12, 50-521-78-12, NUDOCS 7901180030
Download: ML19263B319 (1)


Text

NOV 2 ' 1978 APPENDIX A NOTICE OF VIOLATION Tennessee Valley Authority License Nos.: CPPR-150 CPPR-151 CPPR-152 CPPR-153 Based on the results of the NRC inspection conducted on October 3-5, 1978, it appears that certain of your activities were not conducted in full compliance with NRC requirements as indicated below.

These items have been categorized as described in our correspondence to you dated December 31, 1974.

A.

Section II.B.3 of Attachment B to the Construction Permits required that detailed records of all construction monitoring data will be maintained for use by NRC compliance inspectors and technical staff. The records will contain quarterly summaries documenting the detection of impacts (instances where feedback criteria were exceeded) and, if necessary, the resulting mitigating action and subsequent recovery in water quality.

1.

Contrary to the above, pH of the east holding pond discharge to Dixon Creek was reported to have exceeded the maximum assigned limit of 9.0 on February 14, 15, and 20, 1978; however, no mitigating action subsequent to the release was defined.

2.

Contrary to the above, on March 20, 1978, the licensee failed to report excursion of the east holding pond discharge pH above the maximum assigned limit of 9.0.

The pH recorded was 9.6.

This is a deficiency.

7 9 01 18 0 0 3c>