-rx

/ \\

' emirrmuurrirrn.rrms 1

l f;f.,,[

rf; 5.[,,',

A ONNECTICUT 06101 L <L = = = = = =

January 7, 1980 United States Nuclear Regulatory Commission Office of Inspection and Enforcement Region I 631 Park Avenue King of Prussia, Pennsylvania 19406 ATTENTION: Mr. B. H. Grier, Director Docket No. 50-423 AEC-MP3-201 Gentlemen:

SUBJECT:

Millstone Unit No. 3 I.E. Bulletin No. 79-02, Rev. 2

References:

(1) Letter B. H. Grier to W. G. Counsil Dated November 8,1979.

(2) Letter W. G. Counsil to B. H. Grier Dated July 7,1979.

Reference (1) transmitted the subject Bulletin to Northeast Nuclear Energy Company requesting appropriate action. As a holder of a Construction Permit, the Applicant will cnly respond to Items 1 through 6 of the subject Bulletin Revision.

Item 1 through 4 The information contained in previous submittals is still applicable (Reference (2)).

Item 5 No expansion anchor bolts will be used in concrete block walls to attach piping supports for seismic Category I systems.

Item 6 The Millstone Unit No. 3 design uses base plates in all cases for attachment to concrete walls with expansion anchor bolts.

Structural shapes are not directly bolted with expansion anchor bolts.

Very truly yours, NORTHEAST NUCLEAR ENERGY

.dY Afv7%

William G. Cou~nsil Vice President Nuclear Engineering & Operations cc: Nuclear Regulatory Commission Office of Inspection end Enforcement Division of Reactor Operations Inspection Washington, D. C.

20555 8002230

/ /5 1