Board Notification:Potential Unreviewed Safety Question for LWRs on Interaction Between nonsafety-grade & safety- Grade Sys
ML19262C513
Person / Time
Site: Mcguire, Seabrook, Diablo Canyon, McGuire, 05000514, 05000515, Zimmer, 05000471, 05000467, 05000516, 05000517, 05000580, 05000581, Allens Creek, Atlantic Nuclear Power Plant, Perkins, Black Fox, Green County  
Issue date: 11/26/1979
From: Varga S
Office of Nuclear Reactor Regulation
To: Scott S
NRC OFFICE OF ADMINISTRATION (ADM)
References
TASK-AS, TASK-BN-79-41 BN--79-41, BN-79-41, NUDOCS 8002140186
Download: ML19262C513 (6)


Text

.,

y ~ M x UNIT ED STATES NUCLE AR REGULATORY COMMISSION

[ ',*g

.,f'.

g V. ASHINGT ON, D. C JJS%

q ; ' \\ ' 'y C

S ', x, h j/'E November 26, 1979 MEMORAi4DUM FOR:

Steve Scott, Chief, Document Management Branch, Division of Technical Information and Document Control FROM:

Steven A. Varga, Acting Assistant Director for Light Water Reactors, Division of Project Management

SUBJECT:

BOARD NOTIFICATI0Il - INTERACTIO'l BETWEEN NON-SAFETY AND SAFETY GRADE SYSTEMS (Bit-79-41)

Please provide the enclosed documents to the Board Notification Service Lists for the following cases:

Allens Creek 1 & 2 Perkins Black Fox 1 & 2 Pilgrim 2 Erie 1 & 2 Skagit 1 & 2 Greene County Diablo Canyon 1 & 2 Janesport 1 & 2 McGuire 1 & 2 FMP Zimmer 1 Pebble Springs 1 & 2 Seabrook 1 & 2 f {\\

.)

.o

/

~QhrdhV[$d /

9\\

l Steven-

arga, t{ng Assistant Director for Light Water eactors Division of Project Management Enclosure.

As stated cc:

H. Denton R. Mattson E. Case W. Garmill D. Eisenhut B. Grimes V. Stello, IE J. Stolz D. Vassallo R. Baer R. DeYoung

0. Parr V. Moore L. Rubenstein IE (7)

E. Christenbury L. Ilichols 80 02140 ( $ 6

DISTR 130 TION OF BOARD NOTIFICATIOR ALLENS CREEK BLACK FOX Atomic Safety and Licensing Atomic Safety and Licensing Appeal Board Appeal Board Atomic Safety and I 's oing Atomic Safety and Licensing Board Panel Board Panel Docketing and Service Section Docketing and Sen/ ice Section Texas Public Interest Mr. Alan P. Bielawski Mr. and Mrs. Robert S. Framson Mr. Lawrence Burrell Mr. Robert Alexander Jan Eri. Cartwright Bryan L. Baker Mr. Vaughn L. Conrad Andew T. Dalton, Jr., Esq.

J. Morgan Bishop Mrs. Carrie Dickerson Margaret Bishop Dr. John H. Buck Mr. Gerald F. Diddle, Gen. Mgr.

Dr. E. Leonard Cheatum Mr. T. N. Ewing, Act. Director Carolina Conn Joseph R. Farris, Esq.

J. Gregory Copeland, Esq.

Joseph Gallo, Esq.

Elinore P. Cumings Martha E. Gibbs, Esq.

Stephen A.,Doggett, Esq.

Mr. Maynard Human, Gen. Mgr.

Mr. John F. Doherty Dr. W. Reed Johnson Michael C. Farrar, Esq.

Michael I. Miller, Esq.

R. Gordon Gooch, Esq.

Mr. Paul M. Murphy Robin Griffith Dr. Paul W. Purdom Carro Hinderstein Dr. M. J. Robinson Leotis Johnston Mr. Richard S. Salzman, Chairman Jonathan Kamras Jerome E. Sharfpan, Esq.

Rosemary H. Lemmer Mr. Frederick J. Shon Mr. Gustave A. Linenberger M. Clyde Wisner Richard Lowerre, Esq.

Sheldon J. Wolfe, Esq.

D. Marrack Mrs. Ilene H. Younghein Brenda A. McCorkle Hon. John R. Mikeska ERIE 1&2 Jack R. Newman, Esq.

Charles Andrew Perez Atomic Safety and Licensing Mr. F. H. Potthoff, Ill Board Panel Mr, Wayne Rentfro Atomic Safety and Licens,ng Alan S. Rosenthal, Esq., Chairman Appeal Board Mr. William J. Schuessler Docketing and Service Section Hon. Jerry Sliva, Mayor Elizabeth S. Bowers, Esq.

Glen Van Slyke Dr. Frederick P. Cowan Patricia L. Streilein Thomas A. Kayuha, Esq.

Mrs. Connie Wilson Mr. Frederick J. Shon Sheldon J. Wolfe, Esq., Chairman Jay Silberg, Esq.

Mr. Robert W. Tuf ts Mr. Richard E. Webb

Distribution.

GREET;E COUNTY Ms. Adelaide Flatau Joseph C. Gramer, Esq.

Citizens to Preserve the Hudson Dr. Caryl R. Granttham Dr. W. Reed Johnson Valley Village of Catskill Mr. A. E. Kintigh Atomic Safety and Licensing Frederick H. Lawrence, Esq.

Board Panel Irving Like, Esq.

Atomic Safety and Licensing W. Taylor Reveley, III, E.,.

Appeal Board Richard S. Salzman, Esq.

Docketing and Service Section Dr. Arthur Tamplin Lewis R. Bennett, Esq.

Ms. Jean H. Tiedke Mr. Peter D. G. Brown, Chaiman Edward J. Walsh, Jr., Esq.

Albert K. Butzel, Esq.

Sheldon J. Wolfe, Esq.

Hon Donald Carson Ira Lee Zebrak, Esq.

Hon Edward D. Cohen FNP Jeffrey C. Cohen, Esq.

Dr. Richard F. Cole David H. Engel, Esq.

City of Brigantine Dr. George-A. Ferguson Atomic Safety and Licensing Andew C. Goodhope, Esq.cf Board Panel Mr. John !;ickolitch Atomic Safety and Licensing Ms. Rosemary S. iooler, Ex. Director Appeal Board Arthur L. Reuter, Esq.

Docketing and Service Section Daniel Riesel, Esq.

Mr. Harold P. Abrams William J. Spampinato, Esq.

Mr. Mitchell Attalla

?!ancy Spiegel, Esq.

Glenn 0. Bright, Esq.

Mayor George A. Turner, Jr.

Dr. John H. Buck Algird F. White, Jr.

Vincent W. Campbell, Esq.

Mary M. Cheh, Esq.

JAMESPORT Sanuel J. Chilk, Secretary Troy B. Conner, Jr., Esq.

Enviroraental Protection and Barton Z. Cowan, Esq.

Progress Committee Thomas M. Daugherty, Esq.

Atomic Safety and Licensing John J. Degnan Appeal Board e Michael C. Farrar Esq.

Atomic Safety and Licensing Harold P. Green, Esq.

Board Panel Dr. David L. Hetrick, Professor Docketing and service Section Richard M. Hluchan, Esq.

Ms. Shirely L. Bachrach Keith A. Onsdorff, Esq.

Joel Blau, Esq.

Dr. Glenn L. Paulson Mrs. Laetitia deX. 7radley Robert M. Rader, Eq.

Mr. William C. Chapek Anthony Z. Roisnan, Esq.

Dr. E. Leonard Cheatum Dr. Willard W. Rosenberg Jeffrey C. Cohen, Esq.

Richard S. Salzman, Esq., Chairman Mr. Ralph S. Decker Dr. David R. Schink Carl G. Dworkin, Esq.

Carl Valore, Jr., Esq.

Dr. Harris Fischer James A. Walker, Ex. Director Ellyn R. Weiss, Esq.

Mr. John H. Williamson Sheldon J. Wolfe, Esq., Chaiman

Distribution PEBBLE SPRI!4GS Atomic Safety and Licensing Board Panel Atomic Safety and Licensing Docketing and Service Section Appeal Board William S. Abbott, Esq.

Atomic Safety and Licensing Dr. John H. Buck Board Panel Laurie Burt, Esq.

Dr. A. Dixon Callihan Docketing and Service Section Elizabeth S. Bowers, Esq., Chaiman '

Dr. Richard F. Cole James W. Durham, Esq.

Michael C. Farrar, Esq.

J. Carl Freedman Andew C. Goodhope, Esq.

Donald W. Goda rd, Supa rvisor Henry Hermann, Esq.

Ms. Bernice Ireland Patrick J. Kenny, Esq.

Dr. Walter H. Jordan George H. Lewald, Esq.

Frank Josselson, Esq.

Michael B. Meyer Mr. Lloyd K. Marbet Richard S. Salzman, Esq., Chaiman Dr. William E. Martin, Sr. Ecologist Mr. Lester B. 5,nith Dr. Lawrence R. Quarles Dale G. Stoodley, Esq.

Alan S. Rosenthal, Esq., Chaiman Francis S. Wright Richard S. Salzman, Esq.

Richard M.- Sandvi k, Esq.

.SKAGIT_

Kathleen H. Shea, Esq.

I Canadian Consulate General PERKINS Atomic Safety and Licensing Board Panel Atomic Safety and Licensing Atonic Safety and Licensing g

Board Panel Appeal Board Atomic Safety and Licensing Docketing and Service Section Appeal Board Richard D. Bach, Esq.

Docketing and Service Section Dr. John H. Buck, Member Elizabeth S. Bowers, Esq., Chairman Thomas F. Carr, Esq.

Dr. John H. t.uck Valentine B. Deale, Esq., Chainnan Mrs. Mary Davis James W. Durham, Esq.

Dr. Donald P. deSylva Michael C. Farrar, Esq., Member Dr. Walter J. Jordan Donald W. Godard, Supervisor Quinten Lawson, Esq.

Warren Hastings, Esq.

J. Michael McGarry, III, Es-Dr. Frank F. Hooper, Member William G. Pfefferkorn, Esq.

Roger M. Leed, Esq.

William L. Porter, Esq.

Mr. Nicholas D. Lewis, Chaiman William A. Raney, Jr., Esq.

Mr. Gustave A. Linenbenjer Alan S. Rosenthal, Esq., Chairman Robert Lowenstein, Esq.

Richard S. Salzcan, Esq.

Mr. Lloyd K. Marbet Patrick R. McMullen PILGRIM 2 Alan S. Rosenthal, Esq., Chaiman Richard M. Sandvik, Esq.

Mr. and Mrs. Alan R. Cleeton Robert C. Shofield, Director The Board of Selectmen F. Theodore Thomsen, Esq.

Atomic Safety and Licensing Appeal Board

__ Distribution SEABROOK 1&2 DIABLO CA.'iY0ii Atomic Safety and Licensing Atomic Safety and Licensing Board Panel Appeal Board Atomic Safety and Licensing Atomic Safety and Licensing Board Panel Appeal Board Docketing and Senrice Section Docketing and Service Section Mrs. Elizabeth Apfelberg Robe rt A. Backus, Esq.

Andew Baldwin, Esq.

Leor ard Bickwit, Gen. Counsel Elizabeth S. Boxers, Esq.

Dr. John H. Buck Mr. Glenn D. Bright Laurie Burt, Esq.

Mr..;amuel J. Chilk Herbert H. Brown, Esq.

Philip A. Crane, Jr., Esq.

Thomi s G. Dignan, Jr., Esq.

Mr. Frederick Eissler Micha el C. Farrar, Esq.

David S. Fleischaker, Esq.

E. Te pper Kinder, Esq.

Dr. Kenneth A. McCollom Mrs. Raye Fleming Arthur C. Gehr, Esq.

Alan S. Rosenthal, Esq., Alt. Chairman Mr. Richard B. Hubbard i;oman Ross, Esq.

Dr. W. Reed Johnson Dr. Ernest 0. Salo Yale I. Jones, Esq.

Karin P. Sheldon, Esq.

Janice E. Jerr, Esq.

Ivan W. Smith, Esq.

J. Anthony Klein Joseph F. Tubridy, Esq.

Mr. John Marrs, Managing Ed.

Ms. Elizabeth H. Keinhold Dr. William E. Martin, Sr. Ecologist Bruce fiorton, Esq.

ZIMMER John R. Phillips, Esq.

Alan S. Rosenthal, Esq.

Atomic Safety and Licensing Richard S. Salzman, Esq., Cha1 man Board Panel Mr. James 0. Schuyler Atomic Safety and Licensing Mr. Gordon Silver Appeal Board Mrs. Sandra A. Silver Docketing and Service Section Paul C. Valentine, Esq.

Charles Bechhoefer, Esq., Chairran Mr. Glenn 0. Bright McGUIRE 1&2_

Troy B. Conner, Jr., Esq.

Michael C. Farrar, Esq.

Atomic Safety and Licensing W. Peter Heile, Esq.

Board Panel; Timothy S. Hogan, Jr., Chaiman Atomic Safety and Licensin9 Dr. Frank F. Hooper Appeal Panel Leah S. Kosik, Esq.

Docketing and Service Section David K. Martin, Esq.

Shelley Blum, Esq.

William J. Moran, Esq., Gen. Counsel Michael C. Farrar, Esq.

Dr. Lawrence R. Quarles Dr. Cadet H. Hand, Jr., Director Richard S. Salzman, Esq., Chaiman Robert M. Lazo, Esq., Cha1 man John D. Woliver, Esq.

Dr. Enmeth A. Luebke J. Michael McGarry, III, Esq.

William Larry Porter, Esq.

Jesse L. Riley, President

The enclosed information provides a description of the actions taken to date for operating reactors with regard to a potential unrevie..ed safety question on interaction between non-saftty grade systems and safety grade systems.

Although comparable actions ~have not yet been taken for plants under licensing review we are providing this information to all Boards. This matter will be addressed for these plants and you will be provided with the ongoing staff assessment as it develops.

p. a " g <,

2 c

UNITED STATES

! '4 i

NUCLE AR REGUL A FORY CG*C/.lSSION 3., (. If" J l ',

i vase.cTo.. o. c. nsss bQ4/

\\.'.V ' /

September 17, 1979 ALL OPERATING L'GHT WATER REACTORS

SUBJECT:

POTENTI AL UNREVIEWED S AFETY QUESTICN ON IN~ERACTION EETWEEN NON-SAFETY GRADE SYSTEMS AND SAFETY GRADE SYSTEMS You were infomed by TE Information Notice 79-22, issued Septemaer 14, 1979, that certain r.on-safety grade equipment, if subjemted to an acierse er.vircr-ment, could inpact the safety analyses ar.d the adequacy of the protective functions perfomea by safety grade equipment.

Enclosed is a copy of IE Infomation Notice 79-22, and reprinted copies of an August 30, 1979 Westinghouse letter and a September 10, 1979 Public Service Electric and Gas Company letter which address this matter.

The NRC is concerned that a similar potential may exist at other cperating light water reactor f acilities, including ycurs, for an unreviewed safety natter related to the effects of the environment on control systens result,ng from high energy lir.e breaks inside or outside containment and the results of these effects on the required safety systens.

In accordance with 10 CFR 50.54(f) you are rectested to provide within twenty (20) cays of the date of this letter, written statements, signed under oath or affirmation, which will enable the staff to determine, in light of the concerns discussed above, w" ether or not your NRC license (s) to operate your nuclear power generating facility (ies) should be modified, suspended, or revoked.

Si ncerely, A

m.,

Harold R. Denton, Director Office of Nuclear Reactor Regulation

Enclosures:

1.

IE Infomation Notice 79-22 2.

Westinghcuse's August 30, 1979 Letter (Reprint) 3.

Public Service Electric and Gas Conpany's September 10, 1979 Letter (Reprint) 7 9/03 " O E'

DUPE

r l C :: '.

.%~..

I f

lp UNilED ST.iTES 4@

id NUCLEAR REGULA.70RV UMI5510N OFFICE OF ?NSPECTION AND ENFORCEMENT k'AS H I N';T N'. O. '.

20555 September 14, 1979 IE Infc. -iticn Nctice hc. 75-22 m

QUAllFICATICS OF CGNTROL SYSTEMS Public Service Electric and Gas Ccmpany nctified the L ~.C cf a potential unrevic.ed This nctificaticr was based on a saf ety question at their Saler. Unit I f acility.

continuing review by Vestingncuse of the envircreental qualificaticas of equip;cn; Easec cn the present statuc that they supply for nuc: car steam su;?iy systems.

of this ef fort, b stingncese has irfc~ ec tneir custerers t,a; the perro n3ngg y

an adverse en,tren. cat could impgg; of non-sate}y g-ace equipmenj subqected 10 tne protective f unctions periorme: cy safety grade eq:.iprint.

These non saf et,'

grade systems inciude:

Steam generator pc-cr operated relief valve control system Fressurizer power operated relief valve cont ol syster, 9

Main feersater control syste:

Autcastic rod cor, trol system These systems could potentially malfunction due to a high energy line break NRC is also concerned inat tne adver3e inside or cuiside of containment.

envirorcent could also give erroneous information to the piant operators, Westinghouse states that the consequences of such an event cculd pessibly be mere limiting than results presented in Safety Analysis Reports, ha,ever' v s;inghouse also states that the severity of the results can be limited e

by operator actions together with cperating characterisitics of the safety systecs.

revies their systems to cetermine whether any unreviewed safety questicas exist.

This Information Notice is provic'ec as an early <. ;iicaticn cf a possibiv It is expected that recipients will review the infcEatica significant matter.

for pcssible applicability to their facilities.

No specific actico or response

- re:.ucstec at this tire.

If N;~ evaluations se incicate, further )5:en3ec a.; cn3 may be requested or requ' red.

If jeu nave questicns regardin-this re n-

Offict.

I. case ccntact the Director of tne apprcpriate NRC Regionz

NC ' ritten response to this Inf orration Nctice is required, 7902 U 0I W puPE

s

...;--,,2 a u a.n:

REPR]hT Westingh0Lse Electric Corporation Water Reactor Division Nuclear Service Division Box 2725 Pittsburgh, Pennsylvania 15230 August 30, 1979 PSE-79-21 Mr. F. P. Librizzi, General Manager Electric Production Public Service Electric and Gas Ccnpany 80 Park Place Newark, New Jersey 07101 Dear Mr. Librizzi.

Public Service Electric and Gas Co.

Salem Unit Nc.1 OUALIFICATION CF CONTROL SYSTEMS As pert of a continuing review of the envirar. ental cualifications of Westinghouse supplied NSSS ecuipment, Wes:ingrcuse nas also found it r.ecessary to consider the interaction with non-safety grade systens.

This investigation has been conducted to deterrine if the performance of non-safety grade systems which may not be protected frcr an acverse environment could inpact the protective functicns perforned oy NSSS The NSSS control and protection systems were safety grade equipr.ent.

included in this review to assess the adequacy of the present environ-

r. ental qualification requirements.

As a result of this review, several systems were identified which, if subjected to an adverse environment, could potentially lead to control These systems system operation which may impact protective functions.

are:

Steam generator power operated relief valve control system Pressurizer power operated relief valve contrcl system Main feedwater control system Automatic rod control system 77 // o s e 6 s D u P l=~

Pac.e 2 P S E-7 9-21 Eech of the above nentioned systens coulc potentially na'fu.ction if impacted by adverse environments due to a high energy line break inside or outside containnent.

In each case, a linited set of creaks, coupled with possible consequential control nalfunction in ar ad.erse directicn, of the above events could yield results which are rcre limiting than those presented in the plant Safety Analysis Reports.

In all cases, hcwever, the severity of the results can be linite; by c;erator acticns tcgetner witn operating characteristics of the safety systers.

We believe these systens identified do not constite;e a substantial safety hazard.

However, Westinghouse recommends you revien then to determine if any unreviewed safety cuestions or significant ceficiencies exist in your pl ant ( s).

To assist you in understanding these concerns, Westinghouse will hold a seminar in Pittsburgh on Thursday, September 6 at Westingnouse RIO Center, Building 701,.with all our operating pl ant custerers.

The seninar will address the potential irpect of these concerns for various plant designs and various licensing bases.

Please contact your fNSD Regional Service office to confirn ycur attendance at tha seninar.

We will provide additional detailr. concerr.ing the agenda and other meeting arrangements as they beco e available.

'/ery truly yours,

CRIGINAL SIGNED BY F. Neon, Manager Eastern Regional S WNI Support SR4/CC13314 cc:

H. J. Midura H. J. Heller R. D. Rippe T. N. Tayl or R. A. Uderitz C. F. Barcl ay W

s u ;s >._2 r.2 "T m-

.,m--..,,

,,,, l,. C c -,,, -

et

~ t i.-.c

-.. o-2 rua u..a Saler '..cleir Generatir; 5tation P. O. Eox 55 Har. cod.s Eridge, New Jersey CES35 Septenber 10, 1979 Mr. Ecyce

. Grier D; rector of USi,RC Office of Inspection and Enforcement Pegion I 631 Park Avenue King of Prussia, Pennsylvania 19:06

Dear Sir:

REPCRTASLE OCCURRENCE 79-58/OlP SALEM h0. 1 UNIT LER This lett er will serve to confirn our telephone repcr; to Mr. Gary Schneide> ' f the Regional ',RC office on Fricay, Se;tencer 6,1979, ad. ising of a pctenti al re:criaDie occurrerce in ecccccance witr Technical Specificaticn 6.9.l.5.

a nestinc-We have been notifiec by cur Engineering Departner,t ina

~

house conducted review of the environmental qmalifications of Westinghouse supplied NSSS equipment has identified ina conciticr.s associated with high energy line breaks inside or outside ccr.tainne-and their impact on non-safety control systems nay constitute en unreviewed safety cuestion.

The control systems concerned are stear, generator power operated relief valve control, pressurizer power operated relief valve control, nain feecwater control and astoratic rod control systems.

A detailed report will be subnitted in the time period specified by the Technical Specifications.

Very truly yours, Original Signed By H. J. '<idura Manager - Saler Generatinc Station AWK.jds CC: