Responds to NRC 791009 Request for Clarification of Limit Switch Development for Valves Shown on Util Drawing 0740G30103.Forwards Info Re Limit Switch Development.Torque Switches Will Be Verified During Outage
ML19262A718
Person / Time
Site: Big Rock Point File:Consumers Energy icon.png
Issue date: 12/04/1979
From: Hoffman D
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To: Ziemann D
Office of Nuclear Reactor Regulation
References
NUDOCS 7912100374
Download: ML19262A718 (2)


Text

e.

4%' -

f xx u

Consumers iI

. ; Power Company

' rp' \\\\7 l' '(lt.

i.

1l;:

)!

General Offices: 212 West Michigan Avenue, Jackson, Michigan 49201 e Area Code 517 788-0550 December 4, 1979 Director, Nuclear Reactor Regulation Att Mr Dennis L Ziemann, Chief Operating Reactors Branch No 2 US Nuclear Regulatory Commission Washington, DC 20555 DOCKET 50-155 - LICENSE DPR BIG ROCK POINT PLANT - SEP TOPIC III-10.A,

" THERMAL-0VERLOAD PROTECTION FOR MOTORS OF MOTOR-0PERATEIf VALVES," RESP 3NSE TO REQUEST FOR ADDITIONAL INFORMATION Consumers Power Company was requested by NRC letter dated October 9,1979 to provide a copy of the limit switch development for valves shown on CP Co Drawing 0740G30103. The NRC letter also requested an indication of whether the notation "0T/LS" (open torque / limit switch) on this drawing referred to torque or limit switches.

Forwarded as an attachment to this letter is the requested limit switch development.

Information currently available indicates that the switches identified as "0T/LS" and "CT/LS" are configured to perform as torque switches; this will be verified at a further outage.

If this verification identifies tnat these switches are functioning as limit switches, we will so notify you.

David P Hoffman (Signed)

David P Hoffman Nuclear Licensing Administrator CC JGKeppler, USNRC 1527 506 7912100374-

r The limit switch development for Valves MO-7064, M0-7069, M0-7070, M0-7071 and M0-7072 is:

Switch Valve Position Number Full Open Intermediate Full Closed OT/LS X

X CT/LS X

X OAS1 X

X CASI X

X OAS2 X

X CAS2 X

X IAS2 X

X The limit switch development for Valve M0-7068 is:

Valve Position Contact Full Open Intermediate Full Closed 1

X 2

X 3

X X

4 X

X 5

X 6

X 7

X X

8 X

X X = Indicate-Contact Closed 1527 307