Abnormal Occurrence 75-09:on 750405,snubber Inoperative Due to Fluid Loss.Unit Replaced W/Rebuilt,Tested Unit of Same Size & Stroke.Three Other Units w/BH-1226 Type Snubber Valves Also Replaced
ML19262A234
Person / Time
Site: Crane 
Issue date: 04/07/1975
From: Herbein J
METROPOLITAN EDISON CO.
To:
Shared Package
ML19262A232 List:
References
NUDOCS 7910260573
Download: ML19262A234 (2)


Text

I r

/

//27:2 v 5 " -,..

METROPOLITAN EDISON COMPANY sus.can cicuem rueucuriurrasconocr>riov

/

POST OFrtCE DOX 400 MiO O LETOW N. PENNSYLV ANI A 170G7 TELEPHONE 717 944.4041 Apr'll 7,1975 Uh7?

Mr. J.P. O'Reilly, Director Directorate of Regulatory uf ff e

Regicn I

~

631 Park Aveaue Xing of Prussia, Pa.

19406 Operating License DPR 50 Docket 50-289_

Subject:

Abnorraal Occurrence No. A0 75-09

Dear Mr. O'Reilly:

This telegram is to confinn the telecon with Mr. I.ee Spessard (Region I-CiiO),

and J.J. Colitz (TMI-Unit i Superintendent) at 1000 hours0.0116 days <br />0.278 hours <br />0.00165 weeks <br />3.805e-4 months <br /> 6 April 1975.

The following report is submitted in accordance with paragraph 6.7.2.4.4 (page 6-11) of the technical specifications.

During a routine inspection of the Reactor Building, one snubber, installed at RI-110 (Feedwater to A OTSG, Inside Secondary Shield) was found to be inoperative due to a loss of fluid.

The unit was replaced with a rebuilt, tested unit of the same size and stroke.

In addi tion three other units (located at B1-109 Bl-ll4, and Ri-115) were found to have BH-1226 type snutber valves. (See A0 75 08) These units were reolaced by rebuilt tested units of the sat e size and stroke.

A completo inspection of all other snubbers witnin the secondary shield folicwed the telecon between Lee Spessard and J.J. Colitz and no otner Lindco cylinders

\\

with BH-1226 valves went found to exist within the secondary shield. Durtng tnis follow-up inspection, two snubbers installed at RC-13 and RC-23 (Pressurizer Spray Line) were found to have no oil showing in the signt glass. Both of these snubbers are Basic Engineers units, 3/4' bore, 5" stroke. Botn of these units are in the process of being rebuilt and replaced.

Very truly yours,

j l

J. G. ite rtse.,

1 4

0e3 st1/de:n

~ S ta *.io, Superin tendent f

'91026

7 3

.m i

Mark Hurter Location Malfunction Corrective Action Descriptica

\\

FW-110 A feedwater line inside Loss of fluid Replaced with rebuilt unit of Bore 2 1/2" Secondary Shield (El sa m size and strcke.

Stroke 5" 341).

Mfgr: Grir.r.c11 Cylinder: Lindco Valve: 1226 FW-109 A feedwater line Inside Failure to lockup within Replaced with rebLilt unit of Bore 2 1/2" g

Seconcary Shield (El acceptable range.

sa:ne size and strcke.

Stroke 5" 341).

Mfgr: Grinnell Cylinder: Lindco Vaive: 1226 FW-114 8 feedwater line Inside failure to lockup withi.-

Replaced with rebuilt unit of Bore 21/2" Secondary Shield (El the acceptable range.

same size ar.d stroke.

Stroke 5" 325).

Mfgr: Grinnell Cylinder: Lindco Valve: 1226 FW-115 B feedwater line inside Failure to lockup within Replaced with rebuilt unit of Bore 2 1/2" SecondaryShield(El the acceptable range.

sa:ne size and stroke.

Stroke 5" W

325).

Mfgr: Grinnell Cylinder: Lindco Valve: 1226 CD