ML19261F206

From kanterella
Jump to navigation Jump to search
Environ Incident 74-07:on 740619,free Chlorine Measured at Plant River Discharge in Excess of Limits.Chlorination Addition Rate Reduced
ML19261F206
Person / Time
Site: Crane 
Issue date: 06/20/1974
From: Herbein J
METROPOLITAN EDISON CO.
To:
References
NUDOCS 7910250625
Download: ML19261F206 (1)


Text

.

h MNm A A Jz2"9 y e#

u e e ha s e2_ ma g.

m______.

,m,,

l'i;3. i. T.

bM M%W

.. p i,-. n ',

..a METROPOLliAN EDlSON COMPANY sowoiworcruent nisucummescomunav L A M.;.

c

. /Y'd.a

.i TELEPHONE 717 944 4041 [

ST OFFICE BOX 400 h41DDLETOWN, PENNSYLVANIA 17057 0

JJune 20,1974

. -. b.

Mr. J.P. O'Reilly, Director r

-.. c.

Cto g

. D on { ate of Regulatory 631 Park Avenue

+

King of Prussia, Pa.

19405

'-1

~ '

u. r s.

Operating License DPR-50

,ibcket 50-289 S'ubject: Environrental incident No. EI-74-7 t-c, 2-~

~

Dear Mr. O'Reilly:

h['

,~

This telegram is to confirm the telecon between Lee Spessard (Region I-AEC),

and J.J. Colitz (Station Engineer) at 1200 IMS,19. June 1974.

Violation of the Enviroreental Technical Specification 2.2.1.a (page 7) in that the free chlorine ccmonent measured at the plant river discharge exceeded.1 ppn on 19 June 1974.

Analysis of 'the free chlorine conponent in the plant river discharge 30 minutes after the start of the chlorination cycle indicated.115 ppa and at 50 minutes after the start of the chlorination cycle Inoicatec.i25 ppa.

6 To insure the free chlorine component in the plant river discharge rer,ains below

.1 ppn, the chlorination addition r:te has been reduced to less than 15a Uday.

Very truly yours,

  • !A

.G. Herbein Station Superintendent 1 4 8 1 1 4'8 TMI Nuclear Station JM/dm i791025.0[.98