ML19261F142

From kanterella
Jump to navigation Jump to search
Environ Incident 75-3:on 750417,ETS Violated When Total Residual Chlorine at Plant River Discharge Exceeded Limits for 2-h Period.Sump Pumps Secured Upon Identification of Leak & Contents Treated
ML19261F142
Person / Time
Site: Crane 
Issue date: 04/18/1975
From: Herbein J
METROPOLITAN EDISON CO.
To:
Shared Package
ML19261F137 List:
References
NUDOCS 7910240801
Download: ML19261F142 (1)


Text

.. ;.. ~

/

k?M ~i'i fg,y g

METP.OPOL1 TAN ED1 SON COMPANY SUBSIDIARYCFQENERM.PUBUCUMURESCORPORAn0N IT OFFICE BOX 480 MJDOLETOWN.PENNSYLVANJA 17057 TELEPHONE 717~ 944 4041 f) j-April 18,1975

'//ty~'

c u:

ffr. J.P. O'Reilly, Director 3

7~

~

Directorate of Regulatory Operatinns J

Region 1 6

531 Park Avenue Ring of Prussia, Pennsylvania 19406 Operating 1.fcense DPR-50 Eocket 50-289 Subject-EnvironmentalIncident&}EI75-3 Dear Mr. O'Reilly-This telegram is to confirm the telecen between i.ee Spessard (Region 1-NRC) and J.J.Colitz (TMI Unit I Superintendent) at 1730 hours0.02 days <br />0.481 hours <br />0.00286 weeks <br />6.58265e-4 months <br /> la April 1975.

Violation of the Environmental Technical Specificatica 2.2.'I.c (Page 8) in that the total residual chlorine at the plant river discharge exceeded.01 ppm for greater than two hours an 17 April 1975.

Ca'lculations Jnade following the inadvertent leakage of hypochlorite (used in water treatment) to the industrial waste treatment builcing sump indicate that the chlorine rencentration at the plant discharge was.C4 ppm for a;: proximately three hours.

Analysis results obtained during normal chlorination of the ccoling water sys*m indicate that the cMorice concentration at the plant discharge exceeded.01 ppm for one hour and forty minutes.

Esticates were based on worst possible conditions.

Upon identificatica of the leakage, the sutrp pinnps were secured and the sig contents were treated to remove the chlorine.

s

//

1 A

.G.

rhein Statisa Superintendent 1485 319 um

[

7910240