ARKANSAS POWER & LIGHT COMPANY POST OFelCE BOX 551 LnTLE 70CK, ARKANSAS 72203 (501) 371-40]O June 11, 1979 1-069-5 2-069-1 Mr. Walter P. Haass, Chief Quality Assurance Branch Division of Project Management U. S. Nuclear Regulatory Commission Washington, D. C.

20555

Subject:

Arkansas Nuclear One - Units 1 & 2 Docket Nos. 50-313, 50-368 License Nos. DPR-51, NPF-6 Quality Assurance Program TOPICAL Report ( APL-TOP-1A Rev. 5)

(File:

1510.1,2-1510.1,0233.1) l Ref:

1) Letter W.P. Haass to D. Trimble dated 4/5/79 regarding APL-TOP-1A Rev. 5
2) AP&L letter 049-1 dated 4/17/79 from D. Trimble to W. Haass

Dear Mr. Haass:

Attached (attachment 2) are twenty-five copies of Revision 5 to APL-TOP-1A as requested and addressed by the referenced letters.

AP&L response 9 the staff positions forwarded by reference 1 has been incorporated within each affected page identified by reference 1.

The TOPICAL has not been modified with regard to staff position 421.58 (reference 1).

Our position regarding 421.58 is attached (attachmert 1). Additional infonnation regarding 421.60 is also included in attach-ment 1.

As discussed with Mr. J. Conway of your staff on 5/31/79, AP&L is strong-ly considering the renumbering and title changes of Quality Program procedures used by plant personnel at ANO.

If we conclude that renum-bering and procedure title changes are necessary, these editorial changes will be identified in a future revision of the Topical.

Al so,

as discussed with Mr. Conway, minor, editorial changes have been made to paragraphs 1. 4, 1. 4.1.1. 3, 2. 5. 3, 2. 5. 4. 2, 4. 2. 2, and 18. 5.1 i n ad di tion to paragraphs affected by the staff positions of reference 1.

2307 001 7906190eRYo usueen ucate sour-uriuries sysreu

1-069-5 2-069-1 Mr. Walter P. Haas June 11, 1979 Once NRC approval is obtained, Revision 5 will be dated to coincide with the NRC approval date.

Sincerely,

,0aa e. "KJ David C. Trimble Manager, Licensing DCT:LWH:vb Attachment cc:

Messrs. D. A. Rueter wo/att.

D. R. Sikes M. L. Pendergrass J. M. Griffin J. P. O'Hanlon B. L. Bata 2307 002

ATTACHMENT 1 NRC STAFF POSITION #

RESPONSE

421.58 We consider it to be canpletely unreasonable and un-necessary to test grout material on a daily basis. Grout should only be tested by lot when delivered to the jobsite.

Quite often there is minimal quantity of grout and work involved on a given day, considerably less than the testing itself. Accordingly, our position statement renains the same.

The following is additional justifi-cation for our position.

Prepackaged, non-shrink grout is tested in accordance with the ANSI referenced standards on a per-lot basis.

Proper proportioning and workmanship during placement of non-shrink grout is verified by in-process monitoring in accordance with vendor's instructions.

General use grouts are identical to the various strength, classifi-cation concrete mixes except for the lack of coarse aggregate.

The concrete strength testing program is adequate assurance that grout of the same proportions are satisfactory.

This method of testing grout is currently being used at Midland, Limerick, Susquehanna, and Hope Creek.

NRC I & E have audited the testing program and are satisfied.

421.60 In tables A and B of ANSI N45.2.5, it is stated that

" physical properties of reinforcing steel shall be "per ASTM A615".

However, " physical" properties are distinct from " mechanical" properties.

The physical properties generally include melting point, specific heat, thennal conductivity, etc., and are not specific in ASTM A615.

Therefore, the ANSI statement " physical properties per ASTM A615 is inappropriate.

Practices for the test requirements for the mechanical properties, such as, tensile and bending properties are as described in the po sition.

Ref.

(1):

ASTM Designation A615-72, " Specification for Deformed and Plain Billet Steel Bars for Concrete Reinforcenents",1972.

Ref.

(2):

Regulatory Guide 1.15, " Testing of Rein-forcing Bars for Category I Concrete Structures", December 1972.

Ref.

(3):

ASNE Section III, Div. 2 Code for Concrete Reactor Pressure Vessels and Containments, paragraph CC-2332 (Winter 1977 addenda).

2307 003

Ref.

(4):

ANSI Standard N45.2.5, " Supplementary Quality Assurance Requirements for Installation, In-spection and Testing of Strrctural Concrete and Structural Steel during the Construction Phase of Nuclear Power Plants", July 1974.

2307 004

_