ML19261D196

From kanterella
Jump to navigation Jump to search
Provides Second Interim Rept of 790208 Deficiency Re Vibration in RHR Piping.Variable Spring Supports Added to Valve Operators & One Pipe Support Installed.Vibration Problems Resolved
ML19261D196
Person / Time
Site: Sequoyah  
Issue date: 05/08/1979
From: Gilleland J
TENNESSEE VALLEY AUTHORITY
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
NUDOCS 7905190197
Download: ML19261D196 (1)


Text

TENNESSEE VALLEY AUTHCRITY aui m.ccc4 r = v:,3 c r 2 7 4 n 500C Chestnut Street Tower II MAY 8 1979 Mr. Jarca P. O'2ailly, Diractor Office of Inspection and Enforcement U.S. Nuclear Regulatory Conmission Region II - Suite 3100 101 Marietta Street Atlanta, Georgia 30303

Dear Mr. O'Reilly:

SEQUOY.UI WCLEAR PLtNT UNITS 1.U.D 2 - VIBRATION IU RhR FIPILG -

NCR CEB 79 SECOND INTERIM REFORT The subject deficiency was initially reported to URC-01E Inspector C.

R. McFarland on February 8, 1979. An interin report was aub: itted on March 9, 1979.

We expect to submit our nest report by June 8, 1979.

Tbc variable spring supports have been added to the valve operators, and a pipe support has L in installed to alleviate the pipe vibration problen.

Recesting at the system indicates that the clanging noise and the pipe vibration problems have bcen resolved.

However, ccvere cavitation cccurs during certain modes of operation.

We are investigating the possibility of operating only in modes where cavitation does not occur.

If you have any questions concerning this satter, pleasa ;et in touch with M. R. Wisenburg at FTS 854-2531.

Very truly yours, J. E. Gilleland Assistant Manager of Power cc:

Mr. John G. Davis, Acting Director Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission Washington, DC 20555 gol1 S Io m~ ~, a m ' _.

m.

7905190/ 7 7

' ' ~"