ML19261B160
| ML19261B160 | |
| Person / Time | |
|---|---|
| Site: | Byron |
| Issue date: | 12/15/1978 |
| From: | NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III) |
| To: | |
| Shared Package | |
| ML19261B158 | List: |
| References | |
| 50-454-78-09, 50-454-78-9, 50-455-78-09, 50-455-78-9, NUDOCS 7902140095 | |
| Download: ML19261B160 (2) | |
Text
.
Appendix B
$lh NOTICE OF DEVIATION Docket No. 50-454 Commonwealth Edison Docket No. 50-455 Corpany Based on the inspection conducted on October 31 - November 2, 1978, certain of your activities were not in accordance it appears that with commitments, codes, standards, guides or accept able practices,
as noted below.
Byron /Braidwood PSAR, Table 3.2-2 committed to the requirements of ASME B6PV Code,Section III for the design and fabrication of piping.
ASME B&PV Code,Section III requires that welding be performed in accordance with ASML BEPV Code,Section IX.
1974 Edition,Section III (including 1975 ASME, B6PV Cede, Summer Addenda), Tables NC-2331-1 and ND2331(a)-1 requires a.
specimens for material thickness the Charpy V Notch (C,#) inclusive to have a lateral expansion test over 1 1/2" to 2 1/2" value of 40 mils.
above, on November 2, 1978, the inspector Contary to a.
coupon used in qualifying Hunter established that the test Corporation Welding Procedure Specification (WPS) No. HC-WPS-5 was 2" thick and Calumet Associates Report No. C942-2 indi-cated that C test specimens No. 942-2B and No. 942-2C, taken from the heaE affected rone has a lateral expansion value of 38 mils and 36 mils respectively.
ASME, B6PV Code, 1974 Edition,Section IX (including 1975 Surrer Addenda) Paragraph QW-409.1, states, that "A change 1.
or polarity, or an increase in the in the type of current amperage or voltage" and Table QW-253 lists paragraph QW-409.1 as a Supplementary Essential Variables.
Hunter Corporation WPS No. HC-UPS-5, page 14, states the following:
AWS Filler Metal Size in Classification Inches Volts Amperes _
Pass E7018 3/32 14-18 60-60 Additional fill 1/8 18-22 85-110 E7016 E7018 1/8 18-24 100-140 passes E7018 5/32 22/26 130-180 Final Final 790214007r
Appendix B Contrary to b. above, on November 2, 1978, the inspector estab-lished that the electrical characteristics used in welding the test specimen for the purpose of qualifying WPS No. HC-WPS-5 were as follows:
Pass Amp Volts Size 5
95 20 1/2 3/32 6
110 21 3/32 7
110 21 3/32 8
135 22 1/8 9
135 22 1/8 10 135 22 1/8 11 150 24 1/8 12 145 24 1/8 13 145 24 1/8 14 145 24 1/8 15 150 24 1/8 16 150 24 1/8 17 150 24 1/8 18 145 24 1/8 19 145 24 1/8