ML19260D154

From kanterella
Jump to navigation Jump to search
Revises 790524 Response to NRC Re Violations Noted in IE Insp Repts 50-280/79-08 & 50-281/79-09. Corrective Actions:New Sys Formulated for Controlling Category I Matl from Receipt to Installation
ML19260D154
Person / Time
Site: Surry  
Issue date: 12/19/1979
From: Stallings C
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML18136A470 List:
References
347A, 50-281-79-09, 50-281-79-9, NUDOCS 8002070517
Download: ML19260D154 (4)


Text

.

VinorxA Er.ncrunc Ann Pownu Con swwv 0'

It acnw on n,vx uonn :A 2 0 2 61

'/

December 19, 1979 M,..

/!

q Mr. James P. O'Reilly Serial No.

347A Office of Inspection and Enforcement P0/RMT:baw U. S. Nuclear Regulatory Commission Docke t Nos : 50-280 Region II 50-281 101 Marietta Street, Suite 3100 License Nos: DPR-32 Atlanta, Georgia 30303 DPR-37

Dear Mr. O'Iteilly:

In reference to your Ictter of May 1,1979, and Inspection Report Nos. 50-280/

79-08 and 50-2.31/79-09, further review of the subject non-compliance items has been conducted.

W are forwarding the attached revised response which supple-ments our initial response serial no. 347 dated May 24, 1979.

Very truly yours, 6.24 W r m a y C. M. Stallings Vice President-Power Supply and Production Operations Attachment cc:

Mr. Albert Schwencer 1935 101 y.

8002070 p

77o7ag

RESPONSES TO INFRACTIONS A.

NRC COMMENT:

As required by 10 CFR 50, Appendix B, Criterion XFII, "... records shall be maintained to furnish evidence of activities affecting quality...."

The accepted Quality Assurance Program (FSAR Chapter 17.2), Section 17.2.17 states "These records include plant history; operating logs; principle in part, maintenance and modification activities..."

Contrary to the above, records documenting materials, parts and components used on safety-related co=ponents could not be located in that three of ten maintenance reports completed during 1978 selected at random of three safety-related systems did not provide nor lead to the required traceability of materials used.

B.

ORIGINAL RESPONS2:

The item as stated is correct.

Corrective steps which have been taken and results achieved:

1.

Instructions have been issued to all maintenance and stores personnel that prior to issuance of material from the station storeroom or warehouse, the Maintenance Request No. must be recorded against the This material identification number on stores issue form #97483030.

will insure proper material history associated with safety related systems and component maintenance.

Corrective stens which will be taken to avoid further non-compliance:

2.

The actions taken above will preclude further non-compliance.

3.

The date when full compliance will be achieved:

Full compliance has been achieved.

C.

RESPONSE MODIFICATION Although the action taken in May 1979 was considered adequate at that time to the material traceability problem, subsequent examination of the process correct has shown this not to be the case.

Corrective steps which have been taken and results achieved:

1.

A new system of controlling category I material from its receipt to its installation has been formulated. The program requires that Category I items be tagged during receipt inspection. The tag will remain on the item until its installation, at which time the tag will be removed and affixed to the controlling Maintenance Report.

1935 102

C.

(CONTINUED) 2.

Corrective steps which will be taken to avoid further non-compliance:

The program as outlined above will be instituted and evaluated to determine if it will provide the required traceability of materials used in Safety Related systems.

3.

The date when full coup 11ance will be achieved:

Full conpliance will be achieved by 31 January 1980.

1935 103

,. 8 THIS TICKET TO BE STAPLED TO MAINTENANCE REPORT UPON REMOVAL FROM MATERIAL C AT I NUCLEAR MATERIAL P. O. NO.

ITEM N O.

DATE t!CilVfD INITIALS DAff 855UED INill ALS tiMOVED BY PART NO.

PART NAMI HEAT Of LOT NO.

TRANSFER ALL HEAT OR LOT NUMBERS TO PORTION OF MATERIAL BEING ISSUED 1935 104