ML19259C243
| ML19259C243 | |
| Person / Time | |
|---|---|
| Site: | Fermi |
| Issue date: | 05/10/1979 |
| From: | Hines E DETROIT EDISON CO. |
| To: | James Keppler NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III) |
| References | |
| EF2-46-135, NUDOCS 7906140454 | |
| Download: ML19259C243 (2) | |
Text
1 h-
!!T $"
Quaq Asssa ce Detroit 3331 W B g Bea.e Aras I S O n 3 n ris m "
May 10, 1979 EF2-46,135 Mr. James G. Keppler Regional Director Directciate of Regulatory Operations Region III U.S. Nuclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, Illinois 60137
Dear Mr. Keppler:
Subj ect: Detroit Response to IE Bulletin No. 79-09 This letter is in response to your letter No. 50-341, IE Bulletin 79-09 dated April 17, 1979, which describes undervoltage trip failure in General Electric type AK-2 low voltage power circuit breakers.
Enclosed please find our response to your inquiry in our memorandum EF2-44,652 of May 3, 1979.
Please advise us if you require further action by us regarding this matter.
Sincerely yours, CWLcf n
Enclosure cc:
Mr. John G. Davis, Acting Director Office of Inspection and Enforcement Division of Reactor Inspection Programs U.S. Nuclear Regulatory Commission Washington D.C.
20555 2279 156 Y 161979 7906140//ff
a Detroit Edison
=.
ENRICO FERM1 UNIT 2 PROJECT ENGINEERING RECEIVED f4AY 4 197e May 3, 1979 R. W. CARR EF2 - 44652 To:
R. W. Barr Quality Assurance 206 Engineering Construction-Troy From:
W. F. Colbert Project Engineer - EF2 318 Engineering Construction-Troy
Subject:
Response to IE Bulletin 7909 IE Bulletin 79-09 discusses undervoltage trip failure in General Electric type AK-2 low voltage power circuit breakers.
The failures occurred in the mechanism which links the trip device to the trip shaft assembly. Due to inadequate preventive maintenance, either binding or misalignment of the linkage mechanism. prevented the undervoltage relay from tripping the circuit breaker.
At Enrico Fermi 2, General Electric AK-2 circuit breakers are not used nor are they planned to be used for safety related systems; therefore, no corrective action is required.
Written by:
V. N'agner (f V/
/dk cc:
E. R. Bosetti E. Lusis J. W. Nunley E. F. Wollney Document Control (CLEARS ACTION ITEM 44636) 2279 157