american warming anc ventilating inc
$ 6 - 19 6 - 0 0 0 January 8, 1980 U.S.
Nuclear Regulatory Commission Washington, D.C.
20555 Attn:
Director, Office of Inspection and Enforcement From:
American Warming & Ventilating, Inc.
1310 Indian Wood Circle Maum ee, Ohio 43537
.d j z[ h Subj ect :
Notification of the Existence of a w
y
/,7, td }R Defect per Title 10, Chapter 1, Code O
.7
',.4 jQ of Federal Regulations - Energy, Part 21 Reporting of Defects and Noncompliance
Reference:
Notification Dated 12/07/79 From R.L. Formella, Director Quality Assurance &
Eeliability, ITT General Controls, Glendale, California Gentlemen:
This letter is to keep you informed c f the actions taken by iWV concerning the existence of a defect in a certain spring in some KH91, 92, 94, 95, 96 and 98 Mil 11 ampere Actuators as reported by ITT General Controls.
Enclosed please find copies of Notifications from AET to its aff ected customers.
These Notifications identify the affected projects and tag (identification) numbers -of the affected dampers which have been shipped, 3
,a nf
= : sc.n i
44
.) U D r: sus.. -2: : st
... 11 :-: n =-
- }
I SM I* '
a.
1 -*:55-8 o o i a i o /<t9 _s
U.S. Nuclear Regulatory Com:nission Office of Inspection and Enforcement January 8, 1980 Page 2 You will be copied with all communication /
notification concerning this problem.
Very truly yours, M
Donald E. Sloan Quality Assurance Manager American Warming & Ventilating, Inc.
cc:
W.B.B.
R.L.B.
R.L.A.
J.M.T.
R.J.M.
D.S.L.
1844 507
amencan waimina anc ventilating inc January 8, 1980 Bechtel Assoc. Professional Corp.
P.O. Box.1000 Ann Arbor, MI 48106 Attn:
L.H. Curtis Proj. Engr,
Subject:
Notification of-the Existence of a Def ect in some ITT Actuators per 10 CFR 21
Reference:
Bechtel P.O.
7220-M-337-AC k,( p? N.
Bechtel Job No. 7220 L
Consumers Power Company E
P D
~
Midland Plant
'I, f (y
h.-
AWV Job No. 90235 Gentle =en :
This is.to advise you that American Warming &
Ventilating, Inc. has been notified by ITT General Controls, Glendale, California, under para. 21.21 of 10 CFR 21 Federal Register Vol. 42, No. 108 of the existence of a def ect in a certain spring in some XH91, 92, 93, 94, 95, 96 and 98 Milliampere Hydramotor A ctuat ors.
The nature of the defect, as advised by ITT is that one certain spring, ITT part No. 17443A, used in some NH91, 92, 93, 94, 95, 96 and 98 Mil 11 ampere Hydramotor Actuators has been di.scovered to be manu-f actured from an incorrect material.
It does not possess the designed' strength and will, upon actuation
~
of a greater than 3" stroke take a permanent set.
This results in a decreased force output of approximatel" 160# at all compressed positions.
When these afort mentioned actuators are subjected to an electrical input control signal of zero, the actuator output does not develope the published force when the output shaft
.. -.c...,,..,
...n.....
1844 308
~"
~
Bechtel Absoc. Professional Corp.
L.H. Curtis - Proj. Engr.
January 8, 1980 Page 2 is moved to it's full position.
ITT has also advised that the spring' force output data is incomplete and further tests are being conducted.
AWV will forward data as it is received.
The dampers shipped on the subj ect project af fected by this defect are presented on the attached list.
If you have any questions, please feel free to call.
Very truly yours, l
W Donald E.
Sloan Quality Assurance Manager American Warming & Ventilating, Inc.
cc:
W.3.B.,
J R.'.B.,
R.L.A.,
J.M.T.,
R.J.M.,
D.S.L.
N.M.M. - AWV Project Manager Director, Office of Inspection and Enforcement U.S.
Nuclear Regulatory Commission
~
R. Prendergast -
Bechtel Assoc. Professional Corp.
P.O.
Box 1000 Ann Arbor, MI 48106 J. Marzolf -
Fontanesi & Iann Co.
9000-West Nine Mile Rd.
Oak Park, MI 48237 1
1844
- 09
OmPTICOn WOrmit:0 Onc ventilating inc
Subject:
Notification of the Existence of -
Defect on Some ITT Actuators per 10 CFR 21 Units Shipped On:
Bechtel P.O.
7220-M-336-AC Bechtel Job No. 7220 Consumers Power Company Midland Plant ATV Job No. 90235 DAMPER 'h'AG NO.
DRAWING REF. (SCHED.)
OMO-6 504 A 14055 OMO-6504B 14055 OFV-6505A 14055 OFT-6505B 14055 OFV-6520A 14055 gn y,
ty d j
OFV-6520B 14055 E
OMO-6529A 14055
}p hiNyj Ol!O-6 507A 14055 OMO-6 507B 14055 OMO-6508A 14055 O'.'04 50 8B 14055 OMO-6 509 A 14055 OMO-6 509B 14055 1MO-6559A 14055 l'.10- 6 5 59B 14055 2MO-6559A 14055 2'.!O-6 559B 14055 OMO-5445A 14055 Ol!O-5445B 14055 OMO-6529B 14055 OFV-5444A 14055 OFV-5444B 14055 SIGNED TITLE 8M N
a DATE hu..
B
/h V
s
~
~ ' " ~
l844 310
"amencon warmir:a
~
anc ventilatina inc
~
January 8, 1980 Bechtel Power Corp.
San Francisco Power Division P.O. Box 3965 San Francisco, CA 94119 Attn:
R.H. Elias
Subject:
Notification of the Existence of a Defect in some ITT Actuators per 10 CFR 21
Reference:
Bechtel P.O.
8031-M-113-BC g
!?
d,}'r Limerick Generating Station Bechtel Job 8031
,y %$
AWV Job No. 90186 G ent le=en :
'This is.to advise you that American Warming &
Ventilating, Inc. has been notified by ITT General Co nt rols, Glendale, California, under para. 21.21 of 10 CFR 21 Federal Register Vol. 42, No. 108 of the existence of a def ect in a certain spring in some NH 91, or 93, 94, 95, 96 and 98 Mil 11 ampere Hydramotor Actuators.
The nature of the defect, as advised by ITT is that one certain spring, ITT part No. 17443A, used in some NH91, 92, 93, 94, 95, 96 and 98 Mil 11 ampere Hydramotor Actuators has been discovered to be manu-factured fram an incorrect material.
It does not possess the designed strength and will, upon actuation of a gre,ater than 3" stroke take a permanent set.
This results in a decreased force output of approximately 160# at all compressed positions.
When these afore-mentioned actuators are subjected to an electrical input control signal of zero, the actuator output does not develope the published force when the output shaf t
...s....
" ~
1844 3II
Bechtel Power Corp.
R.H. Elias January 8, 1980 Page 2 is moved to it's full position.
ITT has also auvised that the spring force output data is incomplete and further tests are being conducted.
AWV will forward data as it is received.
The dampers shipped on the subject project affected by this defect are presented on the attached list.
If you have any questions, please feel free to call.
Very truly yours,
- 7L M
Donald E. Sloan Quality Assurance Manager American Warming & Ventilating, Inc.
cc:
W.B.B.,
R.L.B.,
R.L.A.,
J.M.T.,
R.J.M.,
D.S.L.
7 Director, Office of Inspection and Enforcement U.S.
Nuclear Regulatory Commission D.M.
Michaels -
Proj ect Supervisor, Field Procurement Bechtel Power Corp.
P.O.
Box A, Sanatoga Branch Pottstown, PA 19464 M. Rubio -
G.J.
Yamas Co.,
Inc.
1 South Linden Ave.
S. San Francisco, CA 94080 "a
t i844
- 12
amencgn warminq
~
anc ventilating inc
Subject:
Notification of the Existence of a Defect in Some ITT Actuators per 10 CFR 21 Units Shipped On:
Bechtel P.O.
8031-M-113-BC Bechtel Job 8031 Limerick Generating Station AW Job No. 90186 DAMPER TAG NO.
DRAWING REF. (SCHED.)
~
HD 81-041B 13531-45 HD 81-041C 13531-45 HD 81-041D 13531-45 FDC 76-292A 13531-45
-q, f.
FDC 76-292B 13531-45 e
[
d FDC 76-192A 13531-44
('"[*2 3 FDC 76-192B 13531-44 sk
~^-
PDC 78-054 13531-42 PDC 78-055 13531-42 HD,78-018 -
13507-42 HD 78-019 13507-42 HD 78-056 13507-42 HD 76-283A 13507-45 HD 76-283B 13507-45 HD 76-183A 13507-44 HD 76-183B 13507-44 HD 76-193A 13507-44 HD 76-1938 13507-44 HD 78-002A 13507-42 ED 78-002B 13507-42 HD 78-009A 13507-42 HD 78-009B 13507-42 HD 78-037A 13507-42 HD 78-037B 13507-42 HD 78-096A 13507-41 HD'78-096B 13507-41 SIGNED
[S TITLE MA.
Mww f
e
".,,'.',,'.'.,_.w.:..
DATE hu.
8
/pg v
c.
u.-..
1844
- 13
amencan warming anc ventilatina inc January 8, 1980 Bechtel Power Corp.
P. O.
Box 3965 San Francisco, CA 94119 Attn:
Mr. Ed poser Job 8856 Subj ect :
Notification of the Existence of a Defect in some ITT Actuators per 10 CFR 21
Reference:
Bechtel P.O.
8856-M-336 AC
{
h, j Bechtel Job No. 8856 G
Cf Susquehanna Steam Elec. Sta. Units 1 & 2.
~,, Q-]
AWV Job No. 9012f v
y Gentlemen :
e This is to advise you that American Warming &
Ventilating, Inc. has been notified by ITT General Controls, Glendale, California, under para. 21.21 of 10 CFR 21 Federal Register Vol. 42, No. 108 of the existence of a defect in a certain spring in some NE91, 92, 93, 94, 95, 96 and 98 Milliampere Hydramotor Actuators.
The nature of the defect, as advised by ITT is that one certain spring, ITT part No. 17443A, used in some NE91, 92, 93, 94, 95, 96 and 98 Milliampere Hydramotor Actuators has been discovered to be manu-f actured from an incorrect material.
It does not possess the designed-strength and will, upon actuation of a greater than 3" stroke take a permanent set.
This results Tua a decreased force output of approximately 160# at all compressed positions.
When these afore-mentioned actuators are subjected to an electrical input control signal of zero, the actuator output does not develope the published force when the output shaft
'~
i844 214
}b Bechtel Power Corp.
Mr. Ed Poser January 8, 1980 Page 2 is moved to it's full position.
ITT has also advised that the spring force output data is incomplete and further tests are being conducted.
AWV will forward data as it is received, The dampers shipped on the subject project affected by this defect are presented on the attaheed list.
If you have any questions, please feel free to call.
Very truly yours, h
Donald E. Sloan Quality Assurance Manager American Warming & Ventilating, Inc.
cc:
V.S.B.,
R.L.B.,R.L.A.,
J.M.T.,R.J.M.,D.S.L.
D.W. L.
- AWV Proj ect Manager Director, Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission Jack Troy -
Bechtel Power Corp.
P.O. Box 3965 San Francisco, CA 94119 C. Turnbow -
Field Construction Manager Bec,htel Power Corp.
P.O. Box 384 Berwick, PA 18603 Mike Rubio -
G.J. Yamas Co.,
Inc.
1 South Linden Ave.
S.
San Francisco, CA 94080 1844 315
OmeflCan WGmlDQ anc' ventilatina inc
Subject:
Notification of the Existence of a Defect in Some ITT Actuators per 10 CFR 21 Units Shipped On:
Bechtel P.O. 8856-M-336 AC Bechtel Job No. 8856 Susquehanna Steam Elec. Sta. Units 1 & 2 AWV Job No. 90125 DAMPER TAG NO.
DRAWING REF. (SCHED.)
HDM07831A 138.02-1 HDM07831B 13802-1 TDM08271A3 13807-5,6,7 TDMO S271B3 13807-5,6,7 TDM08271C3 13807-5,6,7
@y TDM08271D3 13807-5,6,7 TDM08271A2 13807-5,6,7 L$
TDM08271B2 13807-5,6,7
?>7 if2
-TDMO8271C2 13807-5,6,7 TDM08271D2 13807-5,6,7 TDM08271A1 13807-5,6,7 TDM08271B1 13807-5,6,7 TDM08271C1 13807-5,6,7 TDM08271D1 13807-5,6,7 HDM07801A 13802-1 HDM07801B 13802-1 HDM07821A 13802-1 HDM07821B 13802-1 HDM0754 5 A 13807-1 HDM07545B 13807-1 HDM17657A 13808-1 HDM17657B 13808-1 HDM27630B 13802-1 HDM27657A 13808-5 HDM27657B 13808-5
~
TITLE
[M
// awn he.
g pgo DATE v
.g.
1844 316
aujencen wcumiria anc' %ntilafina inc January 8, 1980 Cincinnati Gac & Electric Company Dayton Power & Light Co.
P.O. Box 960 Cincinnati, Ohio 45201 attn:
Mr. W.W. Schwiers Principal Quality Assurance and Standards Engineer
Subject:
Notification of the Existence of a Defect in some ITT Actuators per 10 CFR 21 x
'P p
0
Reference:
Your P.O. #2354 f:
E Proj ect #4130-00
?
[3 ;$ (( f 0
Wm. H. Zimmer Nuclear Pwr. Sta. - Unit I ATV Job No. 90083 Gentlemep:
This is to advise you that American Warming &
Ven til at in g, Inc. has been notified by ITT General Controls, Glendale, California, under para. 21.21 of 10 CFR 21 Federal Register Vol. 42, No. 108 of the existence of a defect in a certain spring in some NH91, 92, 93, 94, 95, 96 and 98 Mil 11 ampere Hydramotor actuators.
The nature of the defect, as advised by ITT is that one certain spring, ITT part No. 17443A, used in some NH91, 92, 93, 94, 95, 96 and 98 Milliampere Hydramotor Actuators has been discovered to be manu-f actured from an incorrect material.
It does not
- possess the designed strength and will, upon actuation of a greater than 3" stroke take a permanent set.
This results in a decreased force output of approxima+nly 160# at all compressed positions.
When these afore-centioned actuators are subjected to an electrical input control signal of zero, the actuator output does not develope the published force when the output shaf t lF5".
=
1844 JI7 9
h
Cincinnati Gas & Electric Co, Mr. W.W. Schwiers January 8, 1980 Page 2 is moved to it's full position.
ITT has also advised that the spring force output data is incomplete and further tests are being conducted,.
AFV will forward data as it is received.
The dampers shipped on the subject project affected by this defect are presented on the attached list.
If you have any questions, please f eel free to call.
Very truly yours, cr' M^
Donald E.
Sloan Quality Assurance Manager American Warming & Ventilating, Inc.
cc:
W.B.B.,
R.L.B.,
R.L.A.,
J.McT., R.J:M.,
D.S.L.
Director, Of fice of Inspection and Enforcement U.S.
Nuclear Regulatory Commission
~ - ' '
~
J. Cornwell -
Thermatrol, Inc.
P.O.
Box N Cincinnati, Ohio 45231 1844 a18
OfTle: L C10 Wa!Lillfi J anc ventilai-ing inc
Subject:
Notification of the Existence of a Defect in Some ITT Actuators per 10 CFR 21 Units Shipped On:
Your P.O. #2354
~
Proj ect #4130-00 Wm.
H.
Zimmer Nuclear Pwr. Sta. - Unit I AWV Job No. 90083 DAMPER TAG NO.
DRAWING REF. (SCHED.)
[j 1YQ10Y 12467 p
t,'d ' V v.5
$L r
SIGNED
/
pm TITLE M g. Muef
,0cm.
DATE 8
1986
~
1844 319 G
american wof um a anc ventilating inc January 8, 1980 Ebasco Services, Inc.
19 Rector Street New York, NT 10006 Attn:
H.
Parikh
Subject:
Notification of the Existence of a Defect in some ITT Actuators per 10 CER 21
Reference:
Ebasco P.O.
XY-403566 Louisiana Power E Light y
mm g[
CJ A
Waterford Unit #3 OY
?E AWV Job No. 90181 a
5 h
k
~
Gentleren:
Thip is to advise you that American Warming &
Tentilating, Inc. has been notified by ITT General Controls, Glendale, California, under para. 21.21 of 10 C7R 21 Tederal Register Vol, 42, No. 108 of the existence of a defect in a certain spring in some XE91, 92, 93, 94, 95, 96 and 98 Milliampere Hydramotor Actuators.
The nature of the defect, as advised by ITT is that one certain spring, ITT part No. 17443A, used in some NE91, 92, 93, 94, 95, 96 and 98 Milliampere Hydramotor Actuators has been discovered to be manu-factured f' rom an incorrect material.
It does not possess the designed strength and will, upon actuation of a greater than 3" stroke take a permanent set.
This
- results in a decreased force output of approximately 160* at all compressed positions.
When these afore-centioned actuators c.re subjected to an electrical
- input control signal of zero, the actuator output does not develope the published force when the output shaf t
.s 1844
.20
Ebasco Services, Inc.
H. Parikh January 8, 1980 Page 2 is moved to it's full position.
ITT has also advised that the spring force output data is incomplete and further tests are being conudcted.
AWV will forward data as it is received.
The dampers shipped on the subject project affected by this defect are presented on the attached list, If you have any questions, please feel free to call.
Very truly yours, ort A
Donald E.
Sloan Quality Assurance Manager American Warming & Ventilating, Inc, cc:
W.B.B.,
R.L.B.,
R.L.A.,
J.MtT., E.J'.M.,
D.S.L.
T.M. A. - AWV Project Manager Director, Of fice of Inspection and Enforcement U.S.
Nuclear Regulatory Commission W. C.
Oefinger -
Ebasco Services, Inc.
~19 Recotr Street New York, NY 10006 L.A.
Stinson -
Ebasco Services, Inc.
P.O.
Box 70 Kilona, LA 70066 D. Ob er -
D. Ober Associates, Inc.
P.O.
Box 2206 Union, NY 07083 1844
- 21
am. ncan wa! ming i
ano ventilating ire
~
Subject:
Notification of the Existence of a Defect in Some ITT Actuators per 10 CFR 21 Units Shipped On-Ebasco P.O.
hT-403566 Louisiana Power & Light Waterford Unit #3 AWV Job No. 90181 D.WPER TAG NO.
DRAWING REF. (SCHED.)
D-2 (SB) 13341 I ? "r P]
e Mp a
c a,m.
r SIGNED TITLF [M M%q DATE
@m, B
/pgc3 e
g g ew e
1844 22
CYII(~ JU V' ' ' li 3^III ')
5 i
anc ventilatino 1.r January 8,.1980 D. Ober Associates, Inc.
P.O.
Box 2224 1620 Route 22 Union, NJ 07083 Attn:
Dave Ober Subj ect :
Notification of the Existence of a Defect in some. ITT Actuators per 10 CFR 21
Reference:
Cust. P.O.
NY-422617 Ebasco Services, Inc. Agent Florida Power & Light h'
Z St. Lucie #2
(,;}
{p 4
AWV Job No. 90193
\\1
~ ns.a Gentlemen :
This is to-advise you that American Warming &
Ventilating, Inc. has been notified by ITT General Controls, Glendale, California, under para. 21.21 of 10 CFR 21 Federal Register Vol. 42, No. 108 of the existence of a defect in a certain spring in some NH91, 92, 93, 94, 95, 96 and 98 Millimmpere Hydramotor Actuators.
The nature of the defect, as advised by ITT is that one certain spring, ITT part No. 17443A, used in some NH91, 92, 93, 94, 95, 96 and 98 Milliampere Hydramotor Actuators has been discovered to be manu-factured from an incorrect caterial.
It does not possess the designed strength and will, upon actuation of a greater than 3" stroke take a permanent set.
This results_in a decreased force output of approximately 160# at all compressed positions.
When these afore-mentioned actuators are subjected to an electrical input control signal of zero, the actuator output does not develope the published force when the output shaf t s
..,.n....
1844
- 23
D. Ober. Associates, Inc.
Dave Ober January 8,1980 Page 2 is moved to it's full position.
ITT has also advised that the spring force output data is incomplete and further tests are being conducted, AWV will forward data as it is received.
The dampers shipped on the subject project affected by this defect are presented on the attached list.
If you have any questions, please feel free to call.
Very truly yours, c7t Donald E.
Sloan Quality Assurance Manager American Warming & Ventilating, Inc.
cc:
W.B.B.,
R.L.B.,
R.L.A.,
J.M.T.,
R.J.M., D.S.L.
D.W.L.
- AWV Proj ect Manager Director, Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission M.
Calbureanu -
Ebasco Services Two Rector St.
New York, NY 10006
~.
1844 24
afnellCan Warmir!CI anc ventilatina iir
Subject:
Notification of the Existence of a Defect in Some ITT Actuators per 10 CFR 21 Units Shipped On:
Cust.
P.O.
hT-422617 Ebasco Services, Inc, Agent Florida power & Light St. Lucie #2 AWV Job No. 90193 DAMPER TAG NO.
DRAWING REF. (SCHED.)
ny D-29 13470-2,3
~~
D-30 13470-2,3 3 -f rd D-31 13470-2,3 Yf {
4 i;3 D-32 13470-2,3 E
D-14 13470-2,3 D-16 13470-2,3 e
SIGNED
[
m TITLE
[4. Mu em DATE 0m.
8 1986
~~
e 183.4 ;25 ee-a g, n
- r.
.g i:.
e e,
7, ~ -
--2...
ATTf0ED IS A PART 21 WPORT FROM IE 1%IL UNIT - ROOM 359E/W
~
w %i PART 21 IIBITIFICATIm 10. To.190 - oo o C&PANY IFfB vWM IRTE (F LETIER 1/r/ ro DOCET f0.So-3M,"'*' 3 ? 9s ?te 3 rf SPk) 3F' 5
/
/N/ Fo ORIGINAL REPORT I SUPPLB'EITARY IMIE DISTRIRITED DISTRIBKIW:
REtCTOR(P3 Y REL CYCE &
SAFEGUARDS (S) l'ATERIA!3@
NRP/DDR,DIECTOR AD/FFMSI -
AD/SG-IE liRR/DRi DIEf~ TOR ffSS/ FOS AD/ROI AD/PDI ( 2 )
EGIONS REGIONS AD/?CI IE FIES NRR/ DOR,DIPECTOR -
REGI0fG PDR 00ES/SG SS-881 IE FIES G LPDR PDR 8tiP/l FILES CBITPAL FIES-SS-396 LPDR CBiiPAL FIlIS (CKD0 GAL FIES(CHRON)
TERA PDR IE FILES (2) lRR CENTPAL FIES 016 syg-EDBDOUilG,MPA CBM FIES (GB)
B03 DB:iIG, ?PA CENTPAL FILES - SS-396 ACTM-BOBDBEiIG,fPA PRELIfillM EVlMLATION OF THE ATTACHED REPORT INDICATES LEAD RESPONSIBILITY FO FOLLOWiP M S!GN BELorf:
IED telF-ttraL DER SG FFPSI 1844
'26 REV. 6/L3/79