Forwards LER 79-060/03L-0
Date released: 09/27/2019 Download: ML19256F107


LER 79-060/03L-0:on 791020,while Performing Load Test of Diesel Generator 12,operator Unable to Achieve Full Load. Caused by High Exhaust Temp on Cylinder 2 & Clogged Injectors.Injectors Overhauled & Adjusted
ML19256F109
Person / Time
Site: Calvert Cliffs 
Issue date: 11/15/1979
From: Davis S, Pence W
BALTIMORE GAS & ELECTRIC CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
Download: ML19256F109 (2)
Forwards LER 79-060/03L-0
ML19256F106
Person / Time
Site: Calvert Cliffs 
Issue date: 11/15/1979
From: Russell L
BALTIMORE GAS & ELECTRIC CO.
To: GRIER B H
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
Download: ML19256F106 (1)