ML19256E390

From kanterella
Jump to navigation Jump to search
Responds to IE Bulletin 79-01A.Safety-related Sys Include 30 Asco Solenoid Valves.No Valves Susceptible to Loca. Preventive Maint Includes Replacement of Solenoid Coil, Manual Operator & Resilient Parts
ML19256E390
Person / Time
Site: Crane Constellation icon.png
Issue date: 09/27/1979
From: Herbein J
METROPOLITAN EDISON CO.
To: Grier B
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
GQL-1202, NUDOCS 7911050124
Download: ML19256E390 (2)


Text

.... e gg Metropolitan Edison Company (j

Post Off% Boi 542 Reading Pennsylvania 19640 215 929-3601 Writer's Direct Ciel Number September 27, 1979 GQL 1202 Mr. Boyce H. Grier, Director Region I 631 Park Avenue King of Prussia, Pennsylvania 19h06

Dear Sir:

Three Mile Island Nuclear Station, Unit 1 Operating License No. DPR-50 Docket No. 50-289 IE Bulletin 79-01A This letter is in response to your letter of June 6, 1979, and is submitten at this date per our letter of September 10, 1979 (GQL 1130 Restonse 1:

As of the present time there are thirty ASCO solenoid valves in u in safety related systems at TMI-1.

Response 2:

'ine safety systems which the abc<re =entioned valves are a part of include: Makeup and purification, core flood, intermediate cooling, nuclear services closed cycle cooling, chemical addition, vaste disposal-liquid, contain=ent monitoring, air handling, industrial coolant system,vaste disposal - gas and sampling.

There are no ASCO solenoid valves in use at T'4I-1 which could be subjected to a LOCA environ =ent.

Prior to TMI-1 startup or by April 30, 1980, whichever is first, we vill have a pretentive maintenance program such that the solenoid coil, the manual operator (if applicable) and the resilier,t part of the valve are being replaced in accordance with the time period established by the manufacturer and documented as the qualified lif e of the assembled component.

7911050 %

3,) r 7

-) 3 /7 Metropolitan Edison Company is a Member cf the General Public Utilitres System I'JJ L

MR. BOYCE H. GRIER, DIRECTOR GQL 1202 Page 2 Response 3:

Per our letter of June 7, 1979 (GQL Oh22) Met-Ed has met the review and reporting requirements established in IE Bulletin 79-01.

Sincerely, J. G. Herbein Vice President Nuclear-Operations JGH:DGM:mrm 1 qr' 7/O

's.

tGU i