Text

~

-

UNITED ST ATES

d

  • * ,

ATOMIC ENERGY COMMISSION

p

[ N)7 %

DI R ECTO R ATE OF R E GU L A TO R Y OPE R ATION S

.

~

- *

.

631 P AR AVENUE

)9, , N- g* .

KING oF PRUSSI A. PENNSYL.V ANI A 19406

~"#p

JUN 21 y

H. D. Thornburg, Chief, Field Support and Enforcement Branch

Directorate of Regulatory Operations, HQ

RO INSPECTION REPORT No. 50-289 h

"

METROPOLITAN EDISON COMPANY

LICENSE NO. DPR-50

The subject inspection report is forwarded for appropriate Headquarters

action. The action requested is discussed below:

Detail 7 of the inspection report discusses the dilution of the Sodium

Thiosulf ate Tank during recirculation of the Sodium Hydroxide Tank as a

result of leakage thru a normally closed valve and the corrective actions

taken and being considered by the licensee. - We note that the licensee

is acting responsibly to prevent a recurrence of this situation.

Technical Specifications require that each tank be sampled quarterly and

after makeup. The safety implications of this event are that it would

be possible to operate unknowingly with a tank out of specs until the

next sample period. We believe this occurrence has disclosed an apparent

design deficiency which may be generic to B&W designed plants.

(

We recommend that Licensing review this matter for possible backfit

considerations on currently licensed plants and for possible considera-

tion during design review of plants not yet licensed.

The documentation letter and inspection report for this inspection have

been sent to the licensee from this office.

E. J. Brunner, Chief

Reactor Operations Branch

Enclosures:

1.

Copy of Documentation Letter

and Description of Violations

2.

RO Inspection Report No. 50-289/74-25

1449

l46

4-

,

7910180 7 7 5

i