.. _ _. -

es v

License No. DPR-50 APPENDIX A NOTICE OF VIOLATION Based on the results of an NRC inspection conducted on October 11-12, i

1977, it appears that one of your activities was not conducted in full compliance with the conditions of your NRC Facility License No. DPR-50 as indicated below.

This item is categorized as an Infraction.

Technical Specification 4.7.2.1 states "Whenever the control rod drive patch panel is locked (after inspection, test, reprogranining, or main-tenance) each control rod drive mechanism shall be selected from the i

control room and exercised by a movement of two inches or less to verify that the proper rod has responded as shown on the unit computer printout l

of the rod or on the input to the computer for that rod."

Contrary to the above, on May 9,1977, control rods were moved more than i

i two inches (up to 10.7 inches) during the perfonnance of procedure 1301-9.2, Control Rod Program - Special Check, that is used to meet the require-ments of Technical Specification 4.7.2.

3 i

.v f

I.

t 1446 293 4

I t

N 4

7910170

_