ML19256C629
| ML19256C629 | |
| Person / Time | |
|---|---|
| Site: | Point Beach |
| Issue date: | 05/11/1979 |
| From: | Bryan S, Moseley N NRC OFFICE OF INSPECTION & ENFORCEMENT (IE) |
| To: | |
| References | |
| PNO-79-108, NUDOCS 7910100639 | |
| Download: ML19256C629 (1) | |
Text
fi -'!
V
/f'/
PRELIMINARY NOTIFICATION
^
flay 11,1979 PRELIMINARY NOTIFICATION OF EVENT OR UNUSUAL OCCURRENCE--PNO-79-108 This oreliminary notification constitutes EARLY notice of an event of POSSIBLE safety or public interest significance.
The information presented is as initially received without verification or evaluation and i' ' basically all that is known by IE staff on this date.
Far slity:
Wisconsin Electric Power Company, Point Beach 1 and 2 Two Creeks, Wisconsin (DN 50-266; 50-301)
Subject:
LOSS OF COMMUNICATION SYSTEM The licensee informed RIII at 2:00 p.m. yesterday, that while con-ducting a hydrostatic test of the plant fire system, a fitting broke resulting in a loss of fire system pressure and actuation of the emergency diesal fire pump.
Actuation of the diesel fire pump apparently ceased a water hammer, cracking a sprinkler line in a room containir.g plant communications equipment.
The communications equipnent was wetted and caused to be inoperable for a period of two hours.
The backup communications system (radios) was available through-out the event.
The fire system has been returned to normal.
The licensee has issued a press release.
RIII does not intend to issue a press release.
The state of Wisconsin has been notified.
Contact:
SE Bryan, IE x28019; NC t'oseley, IE x2f.50 Distribution:
Transmitted H St -J,1
- 2. c-Chairman Hendrie Commissioner Bradford S. J. Chilk, SECY Commissioner Kennedy Commissioner Ahearne C. C. Kammerer, CA Commissioner Gilinsky ACRS (For Distribution)
Transmitted: f1NE3 L m' P. Bldg ; ^
J. G. Davis, IE L. V Gossick, EF H. R. Denton, f!RR Region V -
H. L. Ornstein, EDO R. C. DeYoung, NRP, J. J. Fcuchard, PA R. J. Mattson, NRR N. **. Haller, f:PA V. Stello, NRR (f1 AIL)
R. G. Ryan, OSP i'. S. Boyd, NRR J. J. Cummings, 0IA H. K. Shapar, ELD SS Bldg.
R. 'linogue, SD W. J. Dircks, NMSS S. Levine, RES PRELIf11 NARY fiOTIFICATION
\\441 2\\\\
781010o 6 3 7